119
External function
Parameter
Setting
External blocking of the com-
pressor; mixer in control
mode or CLOSED
"System definition"
Ó
"Effect of ext. blocking on
heat pump/heating circuits
7015"
"0"
to
"8"
"System definition"
Ó
"Effect of external block-
ing on pumps/compressor
701A"
"0"
to
"31"
Central fault message
No parameters need to be
set.
Cooling function
Cooling function parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
■
"0"
(no cooling)
■
"2"
(natural cooling on cooling
circuit without mixer)
■
"3"
(natural cooling on cooling
circuit with mixer)
■
"4"
(active cooling)
"Cooling"
Ó
"Cooling circuit 7101"
■
"1"
(heating circuit A1/HC1)
■
"2"
(heating circuit M2/HC2)
■
"3"
(heating circuit M3/HC3)
■
"4"
(separate cooling circuit
SKK)
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5609 667 GB
Service
Содержание 7452609
Страница 68: ...68 Removing the top panel 1 Installation sequence Siting the heat pump cont 5609 667 GB...
Страница 125: ...125 Opening the casing door Troubleshooting Maintenance cont 5609 667 GB Service...
Страница 145: ...145 0017 0015 0012 0016 0013 0023 0022 0014 0024 Parts lists Electrical equipment type BWS cont 5609 667 GB Service...
Страница 183: ...183 5609 667 GB...