174
Type BWC in conjunction with "conversion kit for water/
water heat pump"
351.A07
Refrigerant circuit
Refrigerant
R134a
Refrigerant charge
kg
2.35
Permiss. operating pressure, low pressure side
bar
21
MPa
2.1
Permiss. operating pressure, high pressure side
bar
25
MPa
2.5
Compressor
Type
Hermetic scroll
Permiss. operating pressure
Primary circuit
bar
3
MPa
0.3
Secondary circuit
bar
3
MPa
0.3
Dimensions
Total length
mm
844
Total width
mm
600
Total height without programming unit
mm
962
Total height (programming unit open)
mm
1155
Weight
kg
146
Connections
Primary circuit flow/return
G
1½
Secondary circuit flow/return
G
1½
Sound power level
(tested with reference to
EN 12102/EN ISO 9614-2) Weighted total sound pow-
er level at W10
±3
K/W35
±5 K
■ At rated heating output
dB(A)
44
Specification
Specification for water/water heat pumps
(cont.)
5609 667 GB
Содержание 7452609
Страница 68: ...68 Removing the top panel 1 Installation sequence Siting the heat pump cont 5609 667 GB...
Страница 125: ...125 Opening the casing door Troubleshooting Maintenance cont 5609 667 GB Service...
Страница 145: ...145 0017 0015 0012 0016 0013 0023 0022 0014 0024 Parts lists Electrical equipment type BWS cont 5609 667 GB Service...
Страница 183: ...183 5609 667 GB...