79
Pump/component
Parameter
Setting
Remote control (e.g.
Vitotrol 200A)
"Heating circuit 1"
Ó
"Remote control 2003"
or
"Heating circuit 2"
Ó
"Remote control 3003"
"1"
Note
Set code at the Vitotrol 200A
to assign heating circuits:
H1 for heating circuit 1
H2 for heating circuit 2
(see Vitotrol 200A installa-
tion instructions).
Vitocom 100
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension H1
"System definition"
Ó
"External extension
7010"
"1"
Note
For parameters for external
hook-up, see the following
table.
External functions
External functions
Parameter
Setting
External demand
"Internal hydraulics"
, if
applicable
Ó
"Flow temperature for
external demand 730C"
Set flow temperature
for external demand
External starting of the com-
pressor; mixer in control
mode or OPEN
"System definition"
Ó
"Effect of external demand
on heat pump/heating cir-
cuits 7014"
"0"
to
"7"
(Observe parameter
"Flow temperature
for external demand
730C"
)
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5601 429 GB
Service
Содержание 7424689
Страница 83: ...83 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5601 429 GB Service ...
Страница 84: ...84 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 429 GB ...
Страница 85: ...85 Placing the control panel in its service position 4x 2 3 1 Troubleshooting Repairs cont 5601 429 GB Service ...
Страница 86: ...86 Removing the separating plate 1 2 Troubleshooting Repairs cont 5601 429 GB ...