9
Cables
Internal unit
External unit
12 V BUS
1.5 m
1.5 m
43 V BUS
1.5 m
1.5 m
Recommended power cables
Vitocal 200-S, type AWB,
AWB-AC
201.A04
201.A07
201.A10
201.A13
External unit
(compressor)
230 V~
Cable cross-section
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 2.5 mm
2
3 x 4.0 mm
2
Max. cable length
29 m
25 m
16 m
20 m
or
or
Cable cross-section
–
– 3 x 4.0 mm
2
3 x 6.0 mm
2
Max. cable length
–
–
26 m
30 m
Heat pump control unit
(inter-
nal unit) 230 V~
Cable cross-section
■ Without power-OFF
3 x 1.5 mm
2
3 x 1.5 mm
2
3 x 1.5 mm
2
3 x 1.5 mm
2
■ With power-OFF
5 x 1.5 mm
2
5 x 1.5 mm
2
5 x 1.5 mm
2
5 x 1.5 mm
2
Instantaneous heating water
heater
Cable cross-section
■ 400 V~
5 x 2.5 mm
2
5 x 2.5 mm
2
5 x 2.5 mm
2
5 x 2.5 mm
2
■ 230 V~
7 x 2.5 mm
2
7 x 2.5 mm
2
7 x 2.5 mm
2
7 x 2.5 mm
2
Max. cable length
25 m
25 m
25 m
25 m
Overview of possible system schemes
The following table provides an overview
of
all
possible system schemes.
Preparing for installation
Requirements of on-site connections
(cont.)
5601 429 GB
Installation
Содержание 7424689
Страница 83: ...83 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5601 429 GB Service ...
Страница 84: ...84 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 429 GB ...
Страница 85: ...85 Placing the control panel in its service position 4x 2 3 1 Troubleshooting Repairs cont 5601 429 GB Service ...
Страница 86: ...86 Removing the separating plate 1 2 Troubleshooting Repairs cont 5601 429 GB ...