120
Type AWB/AWB-AC
201.A04
201.A07
201.A10
201.A13
Air intake tempera-
ture
Cooling mode
(type
AWB-AC)
■ Min.
°C
15
15
15
15
■ Max.
°C
45
45
45
45
Heating mode
(type
AWB, AWB-AC)
■ Min.
°C
–15
–15
–15
–15
■ Max.
°C
35
35
35
35
Heating water
at 10 K spread
Content (excl. expan-
sion vessel)
l
2.2
2.2
3.2
3.2
Minimum flow rate
(always maintain)
l/h
600
820
1200
1380
Max. external pressure
drop (RFH) at min. flow
rate
mbar
590
540
440
380
Max. flow temperature
°C
55
55
55
55
Electrical values
External unit
■ Rated voltage, com-
pressor
1/N/PE 230 V/50 Hz
■ Max. rated current,
compressor
A
5
9
10
15
■ Starting current,
compressor
A
10.5
15
10
10
■ Starting current,
compressor with
stalled armature
A
20
25
25
32
■ Starting current
(heating of the DC
condensers)
A
45
< 35
30
30
■ Fuse, internal
A
3.5
3.5
3.15
3.15
■ IP rating
IP
24
24
24
24
Specification
Specification
(cont.)
5601 429 GB
Содержание 7424689
Страница 83: ...83 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5601 429 GB Service ...
Страница 84: ...84 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 429 GB ...
Страница 85: ...85 Placing the control panel in its service position 4x 2 3 1 Troubleshooting Repairs cont 5601 429 GB Service ...
Страница 86: ...86 Removing the separating plate 1 2 Troubleshooting Repairs cont 5601 429 GB ...