34
!
Please note
Contamination (such as metal
swarf) or moisture must not enter
the copper pipes.
Therefore, hold the pipe open-
ings down or plug them.
Note
Refrigerant lines of the internal unit are
filled with nitrogen, positive pressure
2 bar.
1.
Remove the nuts from the refrigerant
connections
C
and
D
.
Type AWB/AWB-AC 201.A04:
Replace nuts with union nuts sup-
plied (
⁷
⁄
₁₆
UNF for liquid line, ¾ UNF
for hot gas line). Connect supplied
reducer with copper sealing ring.
Type AWB/AWB-AC 201.A07,
201.A10, 201.A13:
Push the nuts onto the associated
refrigerant lines from the external
unit.
2.
Swage the pipe ends of the refriger-
ant lines.
Note
If solder fittings are used, solder the
fittings using an inert gas.
3.
Fit refrigerant lines and insulate them
to provide protection from heat and
vapour diffusion.
Tighten the nuts with the following torques:
Type
AWB/
AWB-AC
Line
Connection to
internal unit
Torque in Nm
201.A04
Liquid line
7
6 mm
⅝
UNF
with reducer
⁷
⁄
₁₆
x
⅝
14–18
Hot gas line
7
12 mm
⅞
UNF
with reducer
¾ x
⅞
50–62
201.A07
Liquid line
7
10 mm
⅝
UNF
33–42
Hot gas line
7
16 mm
⅞
UNF
63–77
201.A10
Liquid line
7
10 mm
⅝
UNF
33–42
Hot gas line
7
16 mm
⅞
UNF
63–77
201.A13
Liquid line
7
10 mm
⅝
UNF
33–42
Hot gas line
7
16 mm
⅞
UNF
63–77
Installation sequence
Connecting the refrigerant lines
(cont.)
5601 429 GB
Содержание 7424689
Страница 83: ...83 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5601 429 GB Service ...
Страница 84: ...84 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 429 GB ...
Страница 85: ...85 Placing the control panel in its service position 4x 2 3 1 Troubleshooting Repairs cont 5601 429 GB Service ...
Страница 86: ...86 Removing the separating plate 1 2 Troubleshooting Repairs cont 5601 429 GB ...