36
4.
Thermally insulate pipes inside the
building.
5.
Connect the drain hose to the safety
valve.
Connect the drain hose with a slope
and a pipe vent to the public sewer.
Note
■ In underfloor heating circuits, install a
temperature limiter to limit the maxi-
mum temperature for underfloor heat-
ing systems (see page 42)
■ Safeguard minimum flow rate, e.g.
with overflow valve (see Specification
on page 119)
Connecting a cooling circuit if required
For area cooling systems (e.g. under-
floor heating circuit, chilled ceiling), a
contact humidistat (accessory) is
required.
Requirements for the contact humidistat:
■ Electrical connection: 230 V~, 0.5 A
■ Installation inside the room to be
cooled at the cooling water flow
(remove thermal insulation if required)
■ If several rooms with different relative
humidity are part of the cooling circuit,
fit and connect several contact humidi-
stats in series:
Switching contacts as N/C contacts
Electrical connections
Routing electrical cables to the wiring chamber of the internal
unit
Danger
Damaged cable insulation can
cause injury and damage to the
appliance.
Route cables so that they cannot
touch very hot, vibrating or sharp-
edged components.
Danger
Incorrectly routed wiring can lead
to serious injury from electrical
current and result in equipment
damage.
Installation sequence
Connecting a secondary circuit
(cont.)
5601 429 GB
Содержание 7424689
Страница 83: ...83 Opening the programming unit 1 3 2 2x Troubleshooting Repairs 5601 429 GB Service ...
Страница 84: ...84 Removing cover from programming unit if necessary 5 4 4x Troubleshooting Repairs cont 5601 429 GB ...
Страница 85: ...85 Placing the control panel in its service position 4x 2 3 1 Troubleshooting Repairs cont 5601 429 GB Service ...
Страница 86: ...86 Removing the separating plate 1 2 Troubleshooting Repairs cont 5601 429 GB ...