7.1.5 

Charged detection time 

This is the time the “Charged voltage” and “Tail current” must be met in order to consider the battery fully 

charged. 

 

Default setting 

Range 

Step size 

3 minutes 

0 – 100 minutes 

1 minute 

 
7.1.6 

Peukert exponent 

When unknown it is recommended to keep this value at 1.25 (default) for lead acid batteries and change to 1.05 

for Li-ion batteries. A value of 1.00 disables the Peukert compensation. For more information see chapter 8: 

“Battery capacity and Peukert exponent” 

 

Default setting 

Range 

Step size 

1.25 

1.00 – 1.50 

0.01 

 
7.1.7 

Charge efficiency factor 

The “Charge Efficiency Factor” compensates for the capacity (Ah) losses during charging. A setting of 100% 

means that there are no losses.  

 

Default setting 

Range 

Step size 

95% 

50 – 100% 

1% 

The charge efficiency of a lead acid battery is almost 100% as long as no gas generation takes place. Gassing 

means that part of the charge current is not transformed into chemical energy, which is stored in the plates of the 

battery, but is used to decompose water into oxygen and hydrogen gas (highly explosive!). The energy stored in 

the plates can be retrieved during the next discharge, whereas the energy used to decompose water is lost. 

Gassing can easily be observed in flooded batteries. Please note that the ‘oxygen only’ end of the charge phase 

of sealed (VRLA) gel and AGM batteries also results in a reduced charge efficiency. 

A charge efficiency of 95% means that 10Ah must be transferred to the battery to get 9.5Ah actually stored in the 

battery. The charge efficiency of a battery depends on battery type, age and usage. The SmartShunt takes this 

phenomenon into account with the charge efficiency factor. 

 
7.1.8 

Current threshold 

When the current measured falls below the “Current threshold” value it will be considered zero. The “Current 

threshold” is used to cancel out very small currents that can negatively affect the long-term state of charge 

readout in noisy environments. For example, if the actual long-term current is 0.0A and, due to injected noise or 

small offsets, the battery monitor measures -0.05A the SmartShunt might, in the long term, incorrectly indicate 

that the battery is empty or will need to be recharged. When the current threshold in this example is set to 0.1A, 

the SmartShunt calculates with 0.0A so that errors are eliminated. 

A value of 0.0A disables this function. 

 

Default setting 

Range 

Step size 

0.10A 

0.00 – 2.00A 

0.01A 

 
7.1.9 

Time-to-go averaging period  

The time-to-go averaging period specifies the time window (in minutes) that the moving averaging filter works. A 

value of 0 disables the filter and gives an instantaneous (real-time) readout. However, the displayed “Time 

remaining” value may fluctuate heavily. Selecting the longest time, 12 minutes, will ensure that only long-term 

load fluctuations are included in the “Time remaining” calculations. 

 

Default setting 

Range 

Step size 

3 minutes 

0 – 12 minutes 

1 minute 

 

Содержание SmartShunt 1000A

Страница 1: ...EN Manual SmartShunt 500A 1000A 2000A...

Страница 2: ...4 2 Aux connection for monitoring midpoint of a battery bank 8 3 4 3 Aux connection for temperature monitoring 9 3 5 GX device connection 9 4 Commissioning 10 4 1 Download and install VictronConnect 1...

Страница 3: ...averaging period 20 7 1 10 Battery starts synchronised 21 7 1 11 State of charge 21 7 1 12 Synchronise SoC to 100 21 7 1 13 Zero current calibration 21 7 2 Alarm settings 21 7 2 1 SoC alarm setting 2...

Страница 4: ...do in case of an alarm during discharging 31 9 7 The Battery Balancer 31 10 Troubleshooting 32 10 1 Functionality issues 32 10 1 1 Unit is dead no lights on 32 10 1 2 Auxiliary port not working 32 10...

Страница 5: ...mmediately with soap and water If acid enters an eye immediately flood the eye with running cold water for at least 15 minutes and get medical attention immediately Be careful when using metal tools i...

Страница 6: ...used in a wide variety of applications mostly to store energy for later use But how much energy is stored in the battery No one can tell by just looking at it The service life of batteries depends on...

Страница 7: ...TTERY MINUS side of the SmartShunt 3 3 2 Load minus connection Connect the negative of the electrical system to the M10 bolt on the LOAD MINUS side of SmartShunt Make sure that the negative of all DC...

Страница 8: ...rule pin of the red cable with fuse to the SmartShunt by pushing the pin into to the Aux terminal Make sure that the negative of the main battery and the negative of the second battery are common 3 4...

Страница 9: ...minal of the battery Connect the ferrule pin of the red cable with fuse to the SmartShunt by pushing the pin into to the Vbatt terminal Connect the ferrule pin of the black cable to the SmartShunt by...

Страница 10: ...y connected the Bluetooth light stays on After entering the default PIN code VictronConnect will ask you to change the PIN code This is to prevent unauthorizes connections in the future It is recommen...

Страница 11: ...Shunt is by default set to 0 0V The SmartShunt does not automatically detect the system voltage like the BMV does You will need to set the Charged voltage These are the recommended Charged voltage val...

Страница 12: ...eper than 50 The discharge floor can be set to a value between 10 and 20 unless the battery supplier advises otherwise Important warning Lithium batteries are expensive and can be irreparably damaged...

Страница 13: ...e is the best way to monitor the battery A fully charged battery will be indicated by a value of 100 0 A fully discharged battery will be indicated by a value of 0 0 Please note that if the state of c...

Страница 14: ...ed by the battery monitor must be synchronised regularly with the true state of charge of the battery This to prevent drift of the State of charge value over time A synchronisation will reset the stat...

Страница 15: ...tions However the alarm icon is displayed as long as the alarm condition remains Please note that unlike the BMV battery monitor range the SmartShunt does not have an alarm relay or buzzer In case a r...

Страница 16: ...The number of high voltage alarms 5 6 Trends The Trends section of VictronConnect enables datalogging but only while VictronConnect is connected and communicating with the SmartShunt It will simultane...

Страница 17: ...es are Victron devices that provide control and monitoring for all Victron equipment products connected to it Control and monitoring can be done locally but can also be done remotely via our free remo...

Страница 18: ...a VE Smart network you will have to either create a network or join an existing network The setting can be found in SmartShunt settings smart networking Please see the VE Smart network manual for more...

Страница 19: ...charged voltage parameter should be set to 0 2V or 0 3V below the float voltage of the charger Or alternatively see the table below for the recommended setting Recommended settings for lead acid batt...

Страница 20: ...esults in a reduced charge efficiency A charge efficiency of 95 means that 10Ah must be transferred to the battery to get 9 5Ah actually stored in the battery The charge efficiency of a battery depend...

Страница 21: ...rtShunt is reconnected the state of charge will display and will not show 100 until the batteries have been fully charged Please note that leaving a lead acid battery in a partially discharged state f...

Страница 22: ...0 95 0V 0 1V Clear value 1 1V 0 95 0V 0 1V 7 2 3 High voltage alarm When enabled the alarm will activate when battery voltage rises above the set value for more than 10 seconds The alarm will deactiva...

Страница 23: ...r value Default setting Range Disabled Disabled enabled When enabled Default setting Set value 2 0 99 1 Clear value 1 0 99 1 7 2 7 High temperature alarm This setting is only available if the Aux inpu...

Страница 24: ...0 cap F 0 2 0 cap C 0 3 6 cap F 0 1 cap C 0 1 cap F 7 4 Temperature unit setting This setting can be found in the settings of the VictronConnect App itself Leave the SmartShunt by clicking on the arro...

Страница 25: ...ling Bluetooth Bluetooth is enabled by default in the SmartShunt If Bluetooth is not wanted it can be disabled This is done by sliding the Bluetooth switch in the product settings A reason to disable...

Страница 26: ...e This setting can be found in the settings of the VictronConnect App itself Leave the SmartShunt by clicking on the arrow This will bring you back to the device list of the VictronConnect App Now cli...

Страница 27: ...discharge it may only give C2 56Ah Peukert s formula The value which can be adjusted in Peukert s formula is the exponent n see the formula below In the SmartShunt the Peukert exponent can be adjusted...

Страница 28: ...ring voltage in half and comparing the two string voltage halves The midpoint deviation will be small when the battery bank is at rest and will increase At the end of the bulk phase during charging th...

Страница 29: ...tery bank can go unnoticed and could damage all other batteries Always use busbars when applying midpoint voltage monitoring The cables to the busbars must all have the same length Midpoints can only...

Страница 30: ...battery on the midpoint is reduced by half The midpoint alarm level can therefore be set at a lower level 9 4 Alarm delay In order to prevent the occurrence of alarms due to short term deviations tha...

Страница 31: ...tance than others The battery bank may have reached the end of service life or one or more cells or batteries have developed a fault In case of series parallel connection disconnect the midpoint paral...

Страница 32: ...e cable itself and its terminals In case the starter battery is being used make sure that both battery banks have a common negative See paragraph 3 4 1 Aux connection for monitoring the voltage of a s...

Страница 33: ...ion issues see the troubleshooting section of the VictronConnect manual https www victronenergy com live victronconnect start 10 2 2 PIN code lost If you have lost the PIN code you will need to reset...

Страница 34: ...ngs Also see next paragraph Error Reference source not found Error Reference source not found Incorrect state of charge due to incorrect current reading State of charge is calculated by looking at how...

Страница 35: ...ues The SmartShunt does not synchronise automatically One possibility is that the battery never reaches a fully charged state Fully charge the battery and see if the state of charge eventually indicat...

Страница 36: ...State of charge 0 100 0 1 Time to go 1 min Temperature 0 50 C or 30 120 F 1 C F Accuracy of current measurement 0 4 Offset Less than 10 20 40 mA Accuracy of voltage measurement 0 3 INSTALLATION DIMENS...

Страница 37: ...ersion 00 Date March 30th 2020 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 E mail sales victronenergy com www victronenergy...

Отзывы: