background image

27 

 

8  BATTERY CAPACITY AND PEUKERT EXPONENT 

Battery capacity is expressed in Amp hour (Ah) and indicates how much current a battery can supply over time. 

For example, if a 100Ah battery is being discharged with a constant current of 5A, the battery will be totally 

discharged in 20 hours. 

The rate at which a battery is being discharged is expressed as the C rating. The C rating indicates how many 

hours a battery with a given capacity will last. 1C is the 1h rate and means that the discharge current will 

discharge the entire battery in 1 hour. For a battery with a capacity of 100Ah, this equates to a discharge current 

of 100A. A 5C rate for this battery would be 500A for 12 minutes (1/5 hours), and a C5 rate would be 20A for 5 

hours. 

The capacity of a battery depends on the rate of discharge. The faster the rate of discharge, the less capacity will 

be available. The relation between slow or fast discharge can be calculated by Peukert’s law and is expressed by 

the Peukert exponent. Some battery chemistries suffer more from this phenomenon than others. Lead acid are 

more affected by this than lithium batteries are. The SmartShunt takes this phenomenon into account with 

Peukert exponent. 

Discharge rate example 

A lead acid battery is rated at 100Ah at C20, this means that this battery can deliver a total current of 100A over 

20 hours at a rate of 5A per hour. C20 = 100Ah (5 x 20 = 100).  

When the same 100Ah battery is discharged completely in two hours, its capacity is greatly reduced. Because of 

the higher rate of discharge, it may only give C2 = 56Ah. 

 

Peukert’s formula 

The value which can be adjusted in Peukert’s formula is the exponent n: see the formula below. 

In the SmartShunt the Peukert exponent can be adjusted from 1.00 to 1.50. The higher the Peukert exponent the 

faster the effective capacity ‘shrinks’ with increasing discharge rate. An ideal (theoretical) battery has a Peukert 

exponent of 1.00 and has a fixed capacity regardless of the size of the discharge current. The default setting in 

the SmartShunt for the Peukert exponent is 1.25. This is an acceptable average value for most lead acid 

batteries. 

Peukert’s equation is stated below:  

𝐶𝐶𝐶𝐶

=

𝐼𝐼

𝑛𝑛

×

𝑡𝑡

 

where Peukert’s exponent n is:               

𝑛𝑛

=

log

𝑡𝑡

2

log

𝑡𝑡

1

log

𝐼𝐼

1

log

𝐼𝐼

2

 

 

To calculate the Peukert exponent you will need two rated battery capacities. This is usually the 20h discharge 

rate and the 5h rate, but can also be the 10h and 5h, or the 20h and the 10h rate. Ideally use a low discharge 

rating together with a substantially higher rating. Battery capacity ratings can be found in the battery datasheet. If 

in doubt contact your battery supplier. 

 

Calculation example using the 5h and the 20h rating 

The C5 rating is 75Ah. The t

1

 rating is 5h and I

1

 is calculated:             

𝐼𝐼

1

=

75𝐴𝐴ℎ

5ℎ

= 25

𝐴𝐴

    

The C20 rating is 100Ah. The t

2

 rating is 20h and I

2

 is calculated:        

𝐼𝐼

2

=

100𝐴𝐴ℎ

20ℎ

= 5

𝐴𝐴

 

 

The Peukert exponent is:        

𝑛𝑛

=

log 20

log 5

log 15

log 5

= 1.26

  

 

A Peukert calculator is available at  

http://www.victronenergy.com/support-and-downloadssoftware/

 

 

Please note that the Peukert exponent is no more than a rough 

approximation of reality, and that at very high currents, batteries will give 

even less capacity than predicted from a fixed exponent. We recommend 

not to change the default value in the SmartShunt, except in case of lithium 

batteries. 

 

 

 

Содержание SmartShunt 1000A

Страница 1: ...EN Manual SmartShunt 500A 1000A 2000A...

Страница 2: ...4 2 Aux connection for monitoring midpoint of a battery bank 8 3 4 3 Aux connection for temperature monitoring 9 3 5 GX device connection 9 4 Commissioning 10 4 1 Download and install VictronConnect 1...

Страница 3: ...averaging period 20 7 1 10 Battery starts synchronised 21 7 1 11 State of charge 21 7 1 12 Synchronise SoC to 100 21 7 1 13 Zero current calibration 21 7 2 Alarm settings 21 7 2 1 SoC alarm setting 2...

Страница 4: ...do in case of an alarm during discharging 31 9 7 The Battery Balancer 31 10 Troubleshooting 32 10 1 Functionality issues 32 10 1 1 Unit is dead no lights on 32 10 1 2 Auxiliary port not working 32 10...

Страница 5: ...mmediately with soap and water If acid enters an eye immediately flood the eye with running cold water for at least 15 minutes and get medical attention immediately Be careful when using metal tools i...

Страница 6: ...used in a wide variety of applications mostly to store energy for later use But how much energy is stored in the battery No one can tell by just looking at it The service life of batteries depends on...

Страница 7: ...TTERY MINUS side of the SmartShunt 3 3 2 Load minus connection Connect the negative of the electrical system to the M10 bolt on the LOAD MINUS side of SmartShunt Make sure that the negative of all DC...

Страница 8: ...rule pin of the red cable with fuse to the SmartShunt by pushing the pin into to the Aux terminal Make sure that the negative of the main battery and the negative of the second battery are common 3 4...

Страница 9: ...minal of the battery Connect the ferrule pin of the red cable with fuse to the SmartShunt by pushing the pin into to the Vbatt terminal Connect the ferrule pin of the black cable to the SmartShunt by...

Страница 10: ...y connected the Bluetooth light stays on After entering the default PIN code VictronConnect will ask you to change the PIN code This is to prevent unauthorizes connections in the future It is recommen...

Страница 11: ...Shunt is by default set to 0 0V The SmartShunt does not automatically detect the system voltage like the BMV does You will need to set the Charged voltage These are the recommended Charged voltage val...

Страница 12: ...eper than 50 The discharge floor can be set to a value between 10 and 20 unless the battery supplier advises otherwise Important warning Lithium batteries are expensive and can be irreparably damaged...

Страница 13: ...e is the best way to monitor the battery A fully charged battery will be indicated by a value of 100 0 A fully discharged battery will be indicated by a value of 0 0 Please note that if the state of c...

Страница 14: ...ed by the battery monitor must be synchronised regularly with the true state of charge of the battery This to prevent drift of the State of charge value over time A synchronisation will reset the stat...

Страница 15: ...tions However the alarm icon is displayed as long as the alarm condition remains Please note that unlike the BMV battery monitor range the SmartShunt does not have an alarm relay or buzzer In case a r...

Страница 16: ...The number of high voltage alarms 5 6 Trends The Trends section of VictronConnect enables datalogging but only while VictronConnect is connected and communicating with the SmartShunt It will simultane...

Страница 17: ...es are Victron devices that provide control and monitoring for all Victron equipment products connected to it Control and monitoring can be done locally but can also be done remotely via our free remo...

Страница 18: ...a VE Smart network you will have to either create a network or join an existing network The setting can be found in SmartShunt settings smart networking Please see the VE Smart network manual for more...

Страница 19: ...charged voltage parameter should be set to 0 2V or 0 3V below the float voltage of the charger Or alternatively see the table below for the recommended setting Recommended settings for lead acid batt...

Страница 20: ...esults in a reduced charge efficiency A charge efficiency of 95 means that 10Ah must be transferred to the battery to get 9 5Ah actually stored in the battery The charge efficiency of a battery depend...

Страница 21: ...rtShunt is reconnected the state of charge will display and will not show 100 until the batteries have been fully charged Please note that leaving a lead acid battery in a partially discharged state f...

Страница 22: ...0 95 0V 0 1V Clear value 1 1V 0 95 0V 0 1V 7 2 3 High voltage alarm When enabled the alarm will activate when battery voltage rises above the set value for more than 10 seconds The alarm will deactiva...

Страница 23: ...r value Default setting Range Disabled Disabled enabled When enabled Default setting Set value 2 0 99 1 Clear value 1 0 99 1 7 2 7 High temperature alarm This setting is only available if the Aux inpu...

Страница 24: ...0 cap F 0 2 0 cap C 0 3 6 cap F 0 1 cap C 0 1 cap F 7 4 Temperature unit setting This setting can be found in the settings of the VictronConnect App itself Leave the SmartShunt by clicking on the arro...

Страница 25: ...ling Bluetooth Bluetooth is enabled by default in the SmartShunt If Bluetooth is not wanted it can be disabled This is done by sliding the Bluetooth switch in the product settings A reason to disable...

Страница 26: ...e This setting can be found in the settings of the VictronConnect App itself Leave the SmartShunt by clicking on the arrow This will bring you back to the device list of the VictronConnect App Now cli...

Страница 27: ...discharge it may only give C2 56Ah Peukert s formula The value which can be adjusted in Peukert s formula is the exponent n see the formula below In the SmartShunt the Peukert exponent can be adjusted...

Страница 28: ...ring voltage in half and comparing the two string voltage halves The midpoint deviation will be small when the battery bank is at rest and will increase At the end of the bulk phase during charging th...

Страница 29: ...tery bank can go unnoticed and could damage all other batteries Always use busbars when applying midpoint voltage monitoring The cables to the busbars must all have the same length Midpoints can only...

Страница 30: ...battery on the midpoint is reduced by half The midpoint alarm level can therefore be set at a lower level 9 4 Alarm delay In order to prevent the occurrence of alarms due to short term deviations tha...

Страница 31: ...tance than others The battery bank may have reached the end of service life or one or more cells or batteries have developed a fault In case of series parallel connection disconnect the midpoint paral...

Страница 32: ...e cable itself and its terminals In case the starter battery is being used make sure that both battery banks have a common negative See paragraph 3 4 1 Aux connection for monitoring the voltage of a s...

Страница 33: ...ion issues see the troubleshooting section of the VictronConnect manual https www victronenergy com live victronconnect start 10 2 2 PIN code lost If you have lost the PIN code you will need to reset...

Страница 34: ...ngs Also see next paragraph Error Reference source not found Error Reference source not found Incorrect state of charge due to incorrect current reading State of charge is calculated by looking at how...

Страница 35: ...ues The SmartShunt does not synchronise automatically One possibility is that the battery never reaches a fully charged state Fully charge the battery and see if the state of charge eventually indicat...

Страница 36: ...State of charge 0 100 0 1 Time to go 1 min Temperature 0 50 C or 30 120 F 1 C F Accuracy of current measurement 0 4 Offset Less than 10 20 40 mA Accuracy of voltage measurement 0 3 INSTALLATION DIMENS...

Страница 37: ...ersion 00 Date March 30th 2020 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 E mail sales victronenergy com www victronenergy...

Отзывы: