charged voltage, tail current and/or charged time settings. For more information see paragraph 5.3.1: “Automatic 

synchronisation”. 
State of charge does not increase fast enough when charging 

Check if the battery capacity has been set correctly. See paragraph 7.1.1: “Battery capacity”. 
State of charge always shows 100% 

One reason could be that the SmartShunt negative cables have been wired the wrong way around, see 

paragraph 

Error! Reference source not found.

: “

Error! Reference source not found.

”. 

 
10.3.7 

Incorrect voltage reading 

Main battery voltage too low 

Issue with the Vbatt+ cable, perhaps the fuse, the cable itself or one of the terminals are faulty or have loose 

connections. 

Incorrect wiring: the Vbatt+ cable has to be connected to the positive of the battery bank, not midway of the 

battery bank. 

In case a temperature sensor is used, make sure the sensor is connected to the positive terminal of battery bank, 

not midway of the battery bank. 
Starter battery voltage too low 

Issue with the Aux cable, perhaps the fuse, the cable itself or one of the terminals are faulty or have loose 

connections. 
Starter battery voltage missing 

Make sure that both batteries share a common negative. For instruction how to correctly wire the starter battery 

see paragraph 3.4.1: “Aux connection for monitoring the voltage of a second battery”.  

 
10.3.8 

Synchronisation issues 

The SmartShunt does not synchronise automatically 

One possibility is that the battery never reaches a fully charged state. Fully charge the battery and see if the state 

of charge eventually indicates 100%. 

The other possibility is that the charged voltage setting should be lowered and/or the tail current setting should be 

increased. See paragraph 5.3: “Synchronising the SmartShunt”. 
The SmartShunt synchronises too early 

This can be the case in solar systems or other applications with fluctuating charge currents.  Take the following 

measures to reduce the probability for the SmartShunt to prematurely set the state of charge to 100%: 

  Increase the “charged” voltage to slightly below the absorption charge voltage. For example: 14.2V in case of 

14.4V absorption voltage (for a 12V battery). 

  Increase the “charged detection time” and/or decrease the tail current to prevent an early reset due to 

passing clouds. 

  See paragraph 5.3: “Synchronising the SmartShunt”

State of charge indicates three dashes --- : 

This means that  the SmartShunt is in an unsynchronised state. This mainly occurs when the SmartShunt has 

just been installed or after the SmartShunt has been unpowered and powered up again. Charge the batteries and 

the SmartShunt should synchronise automatically. If that doesn't work, review the synchronisation settings, See 

paragraph 5.3: “Synchronising the SmartShunt”. 

If you know the battery is fully charged but don't want to wait until the SmartShunt synchronises then press the 

Synchronise SoC to 100% button, see paragraph 7.1.12: “Synchronise SoC to 100%”. 

 

 

 

Содержание SmartShunt 1000A

Страница 1: ...EN Manual SmartShunt 500A 1000A 2000A...

Страница 2: ...4 2 Aux connection for monitoring midpoint of a battery bank 8 3 4 3 Aux connection for temperature monitoring 9 3 5 GX device connection 9 4 Commissioning 10 4 1 Download and install VictronConnect 1...

Страница 3: ...averaging period 20 7 1 10 Battery starts synchronised 21 7 1 11 State of charge 21 7 1 12 Synchronise SoC to 100 21 7 1 13 Zero current calibration 21 7 2 Alarm settings 21 7 2 1 SoC alarm setting 2...

Страница 4: ...do in case of an alarm during discharging 31 9 7 The Battery Balancer 31 10 Troubleshooting 32 10 1 Functionality issues 32 10 1 1 Unit is dead no lights on 32 10 1 2 Auxiliary port not working 32 10...

Страница 5: ...mmediately with soap and water If acid enters an eye immediately flood the eye with running cold water for at least 15 minutes and get medical attention immediately Be careful when using metal tools i...

Страница 6: ...used in a wide variety of applications mostly to store energy for later use But how much energy is stored in the battery No one can tell by just looking at it The service life of batteries depends on...

Страница 7: ...TTERY MINUS side of the SmartShunt 3 3 2 Load minus connection Connect the negative of the electrical system to the M10 bolt on the LOAD MINUS side of SmartShunt Make sure that the negative of all DC...

Страница 8: ...rule pin of the red cable with fuse to the SmartShunt by pushing the pin into to the Aux terminal Make sure that the negative of the main battery and the negative of the second battery are common 3 4...

Страница 9: ...minal of the battery Connect the ferrule pin of the red cable with fuse to the SmartShunt by pushing the pin into to the Vbatt terminal Connect the ferrule pin of the black cable to the SmartShunt by...

Страница 10: ...y connected the Bluetooth light stays on After entering the default PIN code VictronConnect will ask you to change the PIN code This is to prevent unauthorizes connections in the future It is recommen...

Страница 11: ...Shunt is by default set to 0 0V The SmartShunt does not automatically detect the system voltage like the BMV does You will need to set the Charged voltage These are the recommended Charged voltage val...

Страница 12: ...eper than 50 The discharge floor can be set to a value between 10 and 20 unless the battery supplier advises otherwise Important warning Lithium batteries are expensive and can be irreparably damaged...

Страница 13: ...e is the best way to monitor the battery A fully charged battery will be indicated by a value of 100 0 A fully discharged battery will be indicated by a value of 0 0 Please note that if the state of c...

Страница 14: ...ed by the battery monitor must be synchronised regularly with the true state of charge of the battery This to prevent drift of the State of charge value over time A synchronisation will reset the stat...

Страница 15: ...tions However the alarm icon is displayed as long as the alarm condition remains Please note that unlike the BMV battery monitor range the SmartShunt does not have an alarm relay or buzzer In case a r...

Страница 16: ...The number of high voltage alarms 5 6 Trends The Trends section of VictronConnect enables datalogging but only while VictronConnect is connected and communicating with the SmartShunt It will simultane...

Страница 17: ...es are Victron devices that provide control and monitoring for all Victron equipment products connected to it Control and monitoring can be done locally but can also be done remotely via our free remo...

Страница 18: ...a VE Smart network you will have to either create a network or join an existing network The setting can be found in SmartShunt settings smart networking Please see the VE Smart network manual for more...

Страница 19: ...charged voltage parameter should be set to 0 2V or 0 3V below the float voltage of the charger Or alternatively see the table below for the recommended setting Recommended settings for lead acid batt...

Страница 20: ...esults in a reduced charge efficiency A charge efficiency of 95 means that 10Ah must be transferred to the battery to get 9 5Ah actually stored in the battery The charge efficiency of a battery depend...

Страница 21: ...rtShunt is reconnected the state of charge will display and will not show 100 until the batteries have been fully charged Please note that leaving a lead acid battery in a partially discharged state f...

Страница 22: ...0 95 0V 0 1V Clear value 1 1V 0 95 0V 0 1V 7 2 3 High voltage alarm When enabled the alarm will activate when battery voltage rises above the set value for more than 10 seconds The alarm will deactiva...

Страница 23: ...r value Default setting Range Disabled Disabled enabled When enabled Default setting Set value 2 0 99 1 Clear value 1 0 99 1 7 2 7 High temperature alarm This setting is only available if the Aux inpu...

Страница 24: ...0 cap F 0 2 0 cap C 0 3 6 cap F 0 1 cap C 0 1 cap F 7 4 Temperature unit setting This setting can be found in the settings of the VictronConnect App itself Leave the SmartShunt by clicking on the arro...

Страница 25: ...ling Bluetooth Bluetooth is enabled by default in the SmartShunt If Bluetooth is not wanted it can be disabled This is done by sliding the Bluetooth switch in the product settings A reason to disable...

Страница 26: ...e This setting can be found in the settings of the VictronConnect App itself Leave the SmartShunt by clicking on the arrow This will bring you back to the device list of the VictronConnect App Now cli...

Страница 27: ...discharge it may only give C2 56Ah Peukert s formula The value which can be adjusted in Peukert s formula is the exponent n see the formula below In the SmartShunt the Peukert exponent can be adjusted...

Страница 28: ...ring voltage in half and comparing the two string voltage halves The midpoint deviation will be small when the battery bank is at rest and will increase At the end of the bulk phase during charging th...

Страница 29: ...tery bank can go unnoticed and could damage all other batteries Always use busbars when applying midpoint voltage monitoring The cables to the busbars must all have the same length Midpoints can only...

Страница 30: ...battery on the midpoint is reduced by half The midpoint alarm level can therefore be set at a lower level 9 4 Alarm delay In order to prevent the occurrence of alarms due to short term deviations tha...

Страница 31: ...tance than others The battery bank may have reached the end of service life or one or more cells or batteries have developed a fault In case of series parallel connection disconnect the midpoint paral...

Страница 32: ...e cable itself and its terminals In case the starter battery is being used make sure that both battery banks have a common negative See paragraph 3 4 1 Aux connection for monitoring the voltage of a s...

Страница 33: ...ion issues see the troubleshooting section of the VictronConnect manual https www victronenergy com live victronconnect start 10 2 2 PIN code lost If you have lost the PIN code you will need to reset...

Страница 34: ...ngs Also see next paragraph Error Reference source not found Error Reference source not found Incorrect state of charge due to incorrect current reading State of charge is calculated by looking at how...

Страница 35: ...ues The SmartShunt does not synchronise automatically One possibility is that the battery never reaches a fully charged state Fully charge the battery and see if the state of charge eventually indicat...

Страница 36: ...State of charge 0 100 0 1 Time to go 1 min Temperature 0 50 C or 30 120 F 1 C F Accuracy of current measurement 0 4 Offset Less than 10 20 40 mA Accuracy of voltage measurement 0 3 INSTALLATION DIMENS...

Страница 37: ...ersion 00 Date March 30th 2020 Victron Energy B V De Paal 35 1351 JG Almere PO Box 50016 1305 AA Almere The Netherlands General phone 31 0 36 535 97 00 E mail sales victronenergy com www victronenergy...

Отзывы: