Repeated Absorption Interval (default: 7 days)
The repeated absorption interval, can be set at 1 – 45 days.
Set the DS 3-7
Set the repeated absorption interval Example
DS-8
DS-7
off
DS-6
off
DS-5
off
DS-4 on
DS-3
off
DS-2
DS-1
Determine the required reduced
float time Tq.
Determine the setting number.
Scale = 1 day
Offset = 0
Setting number = Tq
Determine the LED indication.
Press the pushbuttons until the
required LED indication is
displayed.
Required: reduced float time is 1
week.
Setting number = 7.
LED indication =
0
1
0
2
0
2
0
2
0
7
Increments are 1 day.