23
GB
NL
F
D
Appe
ndix
Problem
Cause
Solution
The mains voltage or mains
frequency is out of range.
Ensure that the mains voltage is
between 185 Vac and 265 Vac,
and that the frequency matches
the setting.
The charger is not
functioning
The thermal circuit breaker has
tripped.
Reset the 16 A thermal circuit
breaker.
Incorrect charging current.
Set the charging current at
between 0.1 and 0.2x battery
capacity.
A defective battery connection.
Check the battery terminals.
The absorption voltage has been
set to an incorrect value.
Adjust the absorption voltage to
the correct value.
The float voltage has been set to
an incorrect value.
Adjust the float voltage to the
correct value.
The battery is not
being charged fully.
The DC fuse is defective.
Replace the DC fuse.
The absorption voltage has been
set to an incorrect value.
Adjust the absorption voltage to
the correct value.
The float voltage has been set to
an incorrect value.
Adjust the float voltage to the
correct value.
A defective battery.
Replace the battery.
The battery is too small.
Reduce the charging current or
use a battery with a higher
capacity.
The battery is
overcharged.
The battery is too hot.
Connect a temperature sensor.
Alt. 1: Battery over temperature
(> 50°C)
- Allow battery to cool down
- Place battery in a cool
environment
- Check for shorted cells
Battery charge
current drops to 0
when the
absorption voltage
is reached
Alt 2: Battery temperature sensor
faulty
Unplug battery temperature
sensor from the Multi.
Reset the Multi by switching it
off, then wait for 4 seconds and
switch it on again
If the Multi now charges
normally, the battery
temperature sensor is faulty and
needs to be replaced