6
2. SETTINGS
•
Settings may only be changed by a qualified engineer
•
Carefully read the instructions before changes are made.
•
When setting the charger, all connections to the battery must be
disconnected from the Phoenix Multi or MultiPlus.
•
Do not use non-rechargeable batteries.
•
The Phoenix Multi/ MultiPlus default settings are for charging
Sonnenschein Dryfit A200 gel batteries. For the recommended battery
voltage see section 2.4.
•
Batteries should be placed in a dry and well-ventilated area during
charging.
2.1 Settings – General
2.1.1 Push buttons and dipswitches
A selected number of settings may be changed with the aid of pushbuttons and dip switches
(see Appendix A).
Dipswitches are used to activate set-up, and to determine the setting to be changed. The
value of this setting can be changed with the aid of the pushbuttons.
The value specified is shown on the LEDs. Sections 2.3 describes how the LEDs can be
read.
2.1.2 VEConfigure software
All settings can be changed with VEConfigure.
VEConfigure can be downloaded from www.victronenergy.com
2.2 Default Settings
System
frequency
50
Hz
Inverter
Voltage
230
Vac
Charger
on/
off
on
Charger characteristic
Adaptive with BatterySafe mode
Charging Current
75% of maximum charging current
Battery Type Presets
type 1 (Exide Gel battery)
Absorption Voltage
14.4/ 28.8/ 57.6 Vdc
Absorption Time/ Maximum Absorption Time
4 hours
Float Voltage
13.8/ 27.6/ 55.2 Vdc
Repeated Absorption Time
1 hour
Repeated Absorption Interval
7 days
Bulk
Protection
on
AC Waveform Check
on
Generator/ Shore Current
16 A (optional: 30 A)
PowerAssist (MultiPlus only)
on
3-phase
Setting
off
Master/
slave
slave
(To restore the default settings, both pushbuttons should be held down for 3 seconds while
set-up is activated)