14
2.3.6.5 Absorption Voltage
The absorption voltage can be set at 12-16/ 24-32/ 48-64V. The battery, the T-sense and V-
sense must be disconnected during setting.
Set the DS 3-7
Set the absorption voltage
Example
DS-8
DS-7
off
DS-6
off
DS-5
off
DS-4
off
DS-3
off
DS-2
DS-1
Determine the required absorption
voltage Vq.
Determine the setting number.
Scale = 0.1V
Offset = 12/24V
Setting number = (Vq-
24)/0,1
Determine the LED indication.
Press the pushbuttons until the
required LED indication is
displayed.
Required: absorption voltage is
28.5V.
Setting number= (28.5-24)/0.1 =
45.
LED indication =
0
0
0
1
2
2
2
2
4
5
Increment size is 0.05 V.
2.3.6.6 Absorption Time/ Maximum Absorption Time (default: 4 hours)
This setting defines the absorption period in the case of the fixed charging characteristic
and the maximum absorption time in the case of the adaptive charging characteristic.
The (maximum) absorption time can be set from 1 to 8 hours.
Set the DS 3-7
Set the (maximum) absorption time Example
DS-8
DS-7 on
DS-6
off
DS-5 on
DS-4 on
DS-3
off
DS-2
DS-1
Determine the required (maximum)
absorption time Tq.
Determine the setting number.
Scale = 1 hour
Offset = 0
Setting number = Tq
Determine the LED indication.
Press the pushbuttons until the
required LED indication is
displayed.
Required: (maximum) absorption
time is 4 hours.
Setting number = 4.
LED indication =
0
0
0
0
0
2
0
2
0
4
Increments are 1 hour.