AC POWER
Important Safety Instructions
DANGER!
Adhere to the “Important Safety Instructions” presented at the front of this document.
Safety Precautions
DANGER!
RISK OF ELECTRICAL SHOCK, GENERAL
All ground connections must be installed and verified, prior to connecting any power cables (AC or DC)
and turning-up of the WIC.
Before installation, the AC grounding electrode system must be bonded to an AC main service power
neutral/ground bus. Contact your local power company or local practices for information about codes or
restrictions for your installation.
When connecting any discrete power connection, make the connection first with the ground/return and
break last with ground/return.
Remove rings, metallic wrist bands, or bracelets, etc.
DANGER!
RISK OF ELECTRICAL SHOCK, AC
Proper actions, include, but not limited to:
a)
Verify before contacting the WIC that no current leakage or ground fault condition is present.
b)
Verify a proper ground is in place.
c)
Verify for AC hook-up, all WIC circuit breakers are OFF and the utility incoming feed is OFF.
Use a trained licensed electrician.
DANGER!
ELECTRICAL HAZARD
Observe all safety precautions as specified by local building codes and the National Electrical Code
(NEC). All procedures should be performed by a licensed electrician. If local building codes specify
procedures different from those in this section, follow local codes.
General
Refer to “Grounding the WIC” on page 82 for information on WIC grounding.
WIC AC Schematic
The complete system schematics are included with each WIC.