External DC Generator Wiring
Generator Input Circuit Breaker Kit P/N 564219 is shipped loose with the WIC. Refer to IM564219 (Kit
Installation Instructions) to install the kit into the NetSure Power System. This kit provides a 400 A circuit
breaker to feed the rectifier output bus of the power system through a shunt. The customer connects an
external generator output to this circuit breaker which then supplies generator input power to the system.
Procedure
Recommended Cable Sizes
•
0 to 150 Feet: One (1) 500 kcmil or two (2) 4/0 per polarity.
•
Greater than 150 Feet: One (1) 750 kcmil per polarity.
Recommended Cable Routing
1.
DC generator cables enter the WIC either via the knock outs located on the rear of the base or via the
knock outs located on the bottom of the base. See
2.
DC generator cables are routed up through the knock outs provided in the interior floor of the WIC. The
cables then are routed up the cable ladder on the rear wall, then to the ladder rack on the adjacent wall,
then transition to the ceiling ladder rack, and then down into the NetSure Power System. See
Connecting DC Generator Cable to Generator Input Circuit Breaker Kit P/N 564219
1.
Wire input generator leads per
o
Load should not exceed 75% of the 400 A breaker rating (300 A).
o
Designed to accommodate two cables (per polarity), minimum wire size is equivalent to one (1) 500 kcmil cable
(each polarity).
o
Maximum lug width is 1.25”.
Operating the Power System
Refer to the DC power system instruction manual(s) for information regarding the powering and operation of
the power system. Refer to