Chapter 1 Product Introduction
RDU501 Intelligent Monitoring Unit User Manual
Input power
There are two isolated power inputs on the rear panel of the RDU501 main unit. The location is shown in Figure 1-1.
The power input parameters are shown in Table 1-1.
Table 1-1 Power input parameters
Power
Input
Range
Interface
AC Input
Voltage
100Vac to 240Vac
C14 with break-away prevention feature
Current
<2A
Frequency
50/60Hz
Indicators
The rear panel of the RDU501 has four indicators. The location is shown in Figure 1-1. See Table 1-2 for definitions.
Table 1-2 Definitions of rear panel indicator
Silk Screen Printing
Color
Status
Description
Power1
Green
On
RDU501 power supply 1 is on
Off
RDU501 power supply 1 is off
Power2
Green
On
RDU501 power supply 2 is on
Off
RDU501 power supply 2 is off
Link
Green
On
Correct connection
Off
Wrong connection or disconnected
Speed
Yellow
On
1000Mbps rate
Off
No rate
Figure 1-1 shows the positions of the indicators on the front panel of the RDU501 main unit. See Table 1-3 for
definitions.
Table 1-3 Definitions of front panel indicator
Silk Screen Printing
Color
Status
Description
Run/Alarm
Green /Red
Green
No alarm
Red
Alarm
COM/Sensor
Green
Blink
Receiving data
Off
No data received
Yellow
Blink
Transmitting data
Off
No data transmitted
DI/AI/DO/AO/Smoke
Green
On
External device is connected
Off
No external device is connected or the port is short circuited
Reset button
Press and hold the reset button (Silk Screen Printing is “Reset”) for more than 4 seconds. After the device emits a
“beep” sound, the RDU501 will restore the IP address and password to the factory default after it is restarted. The
default values are shown in Table 1-4.
USB port
The RDU501 main unit provides four ports of USB-A socket type, which can be connected to the USB Modem of the
specified model, as well as the keyboard and mouse. The location is shown in Figure 1-1.
Ethernet port
The RDU501 main unit provides two network ports and one fiber port. The 10/100/1000M Ethernet port is used.
Figure 1-1 shows the 1000M fiber. Table 1-4 lists the default network port configuration.
Table 1-4 Network port default configuration parameters
Parameter
Network card number
IP address
Subnet code
Default gateway
Ethernet card1
(
eth0)
192.168.0.254
255.255.255.0
192.168.0.1
Ethernet card 2
(
eth1)
192.168.1.254
255.255.255.0
192.168.0.1
Optic fiber port
192.168.2.254
255.255.255.0
192.168.0.1
Note: The default password for terminal background and web browser login is “Vertiv”