Chapter 3 Web Interface of RDU501
RDU501 Intelligent Monitoring Unit User Manual
Figure 3-31 Fire fighting management
Each fire fighting device has up to 4 DI signals, and the four DI signals are: power failure signal, internal fault signal,
fire alarm signal, gas discharge signal, and they are all connected through an IRM-4DI sensor, the address of the 4DI
sensor is F1 (User mode). Fire fighting access is achieved by adding a firefighting device
(ENP_ENV_FIREFIGHTING[SENSOR]) in the Power and Environment Device Management page.
3.4.3 IT Management
IT management monitors and manages IT equipment through IPMI device management, console device
management, and server shutdown management.
In the RDU501 homepage, click on the IT Management menu to see seven submenus, including:
IPMI Device List,
IPMI Device Management, IPMI Device Alarms, Console Device List, Console Device Management, Console
Log Data,
and
Server Shutdown Management
.
IPMI Device Management
Click the
IPMI Device List
submenu under the
IT Management
menu to open the page shown in Figure 3-32. The
icon color in the device card indicates the status of the device. When the communication is normal, it is displayed in
green. When the communication fails, it is grayed out. When the device has an alarm, it is displayed in red.
1. IPMI device detailed information
Figure 3-32 IPMI Device List
Click on the card in the IPMI device list to enter the device detailed information page, which displays the device
Overview
page by default. The device
Overview
page displays basic information, shortcut menus, version
information, and the latest event log of the IPMI device, as shown in Figure 3-33.
The running status is divided into normal and alarm. The icon
is displayed in the normal state and the icon
is
displayed in the alarm status.