Vertiv
|
NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C)
|
Rev. A
9
INTRODUCTION
The R48-2000 C provides a rectifier mounted inside an environmentally protective enclosure. The
R48-2000 C can be wall or pole mounted.
Ordering Structure
What is in the Box
Refer to Table 1.
Table 1:
ITEM
(1) 21505943 Pole/Wall mount Kit(1x)
①
63240BQ0 Mounting Bracket (Small)(1x)
②
63240BPY Mounting Bracket (Big)(2x)
③
63126330 Pole Mount Band(2x)
④
26011356 M5 Flat Head Screws(3x)
⑤
26011153 M8 Bolts w/ Flat Washer and Lock Washer(2x)
⑥
26011018 M5 Bolts w/ Flat Washer and Lock Washer(6x)
(
2
) 21505942 Front Side shield Kit(1x)
①
26011383 M6 Bolts w/ Flat Washer and Lock Washer(4x)
②
63240BPM Front Side Shield(1x)
③
63128427 Securing Colume(4x)
(3) UM1R482000C Installation and User Manual(1x)
Rectifier Overview
The rectifier provides load power during normal operating conditions. The rectifier is a constant
power design. The rectifier is rated at its maximum output power. This means that, within the
normal operating ambient temperature range and input voltage range, the maximum available
output power is a constant 2000 W. Within these ranges, the rectifier operates in one of three
modes, depending upon load demands. Transition between modes is completely automatic. If
ambient temperature rises above or input voltage falls below acceptable values, the rectifier
continues to operate but at derated output power levels.
•
Constant Voltage Mode:
For any initial output voltage setting from -42 VDC to -58 VDC
(factory set at -54 VDC), output voltage remains constant regardless of load. This is the
normal operating condition, in which loads are being supplied. The rectifier operates in the
Constant Voltage Mode unless load increases to the point where the product of load current
and output voltage is approximately 2000 W.
•
Constant Power Mode:
As load increases above approximately 2000 W (non-adjustable),
output current continues to increase, but output voltage decreases as required to maintain
constant output power. The rectifier operates in the Constant Power Mode unless load
continues to increase to the point where the current limit setting is reached.
•
Constant Current Mode:
If load increases to the current limit setting, output voltage
decreases linearly to maintain output current at the current limit setting.
Rectifier Specifications
The specifications are for a single unit only, unless otherwise noted.