Vertiv
|
NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C)
|
Rev. A
15
Figure 6: Efficiency Curve (@ 120 VAC, 60 Hz)
Environmental Ratings
1.
Operating Ambient Temperature Range:
a) -40 °C (-40 °F) to +50 °C (+122 °F) with full power performance.
b) +50 °C (+122 °F) to +75 °C (+167 °F) with derating output.
c)
Temperature Coefficient:
0.02 % per degrees Celsius.
2.
Storage Ambient Temperature Range:
-20 °C (-4 °F) to +55 °C (+131 °F).
3.
Relative Humidity:
This rectifier is capable of operating in an ambient relative humidity range of
0 to 90 %.
4.
Altitude:
3048 m (9842 feet).
5.
Surge Protection:
EN61000-4-5 up to level 4, Telcordia GR-1089-Core, IEEE C62.41-2002,
YD/T 731-2002.
Performance Criteria B.
AC Power Terminals
TEST LEVEL
SOURCE
IMPEDANCE
PERFORMANCE
CRITERIA
LINE TO LINE
LINE TO GROUND
± 4 kV
± 4 kV
2 ohms
B
NA
± 6 kV
12 ohms
B
DC Power Terminals:
TEST LEVEL
SOURCE
IMPEDANCE
PERFORMANCE
CRITERIA
LINE TO LINE
LINE TO GROUND
± 500 V
± 500 V
2 ohms
B
± 800 V
± 800 V
2 ohms
B
The test method is described in EN 61000-4-5. In this test the DC-cables shall be 5 m long.
6.
Single Rectifier Audible Noise:
At 25 °C ≤45 dB(A). Measurement made at 0.6 m distance in
front of rectifier and at same horizontal line of the middle of rectifier.
75.0
80.0
85.0
90.0
95.0
0
20
40
60
80
100
E
ff
ici
e
n
cy
(%)
Load(% of rated load)
Efficiency Curve
Содержание R48-2000C
Страница 37: ......
Страница 38: ...VertivCo com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1R482000C RH 03 25 ...