Vertiv
|
NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C)
|
Rev. A
28
4. Install the cord to the Terminal block then screw the screws of the terminal block as required.
Figure 20: Customer Wiring Diagram.
Alarm
DC output 1
DC output 2
DC output 3
Battery
AC input
Alarm
Cable info: UL2464 22AWG 8/C
Maximum cable diameter is 6mm
(0.24inch)
Cable gland information
Designation Vertiv P/N
Alarm 63204186
DC OUTPUT1 63204183
DC OUTPUT2 63204183
DC OUTPUT3 63204185
Battery 63204185
AC INPUT 63204183
DC OUTPUT1
、
DC OUTPUT2
Cable info:SJOOW 12AWG 2/C
Maximum cable diameter is 9mm to
16mm (0.35inch to 0.63inch)
DC OUTPUT3
、
Battery
Cable info:SOOW 6AWG 2/C
Maximum cable diameter is 18mm to
25mm (0.71inch to 1inch)
AC INPUT
Cable info:SJOOW 12AWG 3/C
Maximum cable diameter is 9mm to
16mm (0.35inch to 0.63inch)