Vertiv
|
NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C)
|
Rev. A
10
DC Output Ratings
1.
Voltage:
-42 VDC to -58 VDC, positive ground. Output voltage is factory set at -54 VDC.
2.
Output Power and Current:
a) 2000 W (41.7 A) @ 200 VAC to 250 VAC input and -48 VDC output.
3.
Output Characteristics:
Refer to Figure 1 for a graph of output voltage vs. output current.
Figure 1: Output Voltage vs. Output Current
4.
Power Derating Based on Input Voltage:
The rectifier power varies with changes in input
voltage. It uses an advanced power limitation method. The lower input threshold is 85 VAC. The
rectifier can provide its maximum rated power (2000 W) as long as the input voltage is within the
range of 176 VAC to 300 VAC. Below 176 VAC, and down to 85 VAC, the rectifier will continue to
operate normally but will be in a power derating mode. The relationship between the output
power and input voltage is illustrated in Figure 2.
Figure 2: Power Derating Based on Input Voltage
0
10
20
30
40
50
60
0
5
10
15
20
25
30
35
40
45
O
u
tp
u
t
V
o
lta
ge
(V
)
Output Current (A)
Output voltage v.s. Output current at max. Power
0.0%
20.0%
40.0%
60.0%
80.0%
100.0%
120.0%
0
50
100
150
200
250
300
350
%
o
f
o
u
tp
u
t
p
o
w
e
r
Input voltage (Vac)
Output power vs. Input voltage and Vo>48V at Temp
≤4
5
℃
Содержание R48-2000C
Страница 37: ......
Страница 38: ...VertivCo com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA UM1R482000C RH 03 25 ...