NetSure R48-2000C Outdoor Rectifier Installation & User Manual (UM1R482000C)
|
Rev. A
12
For any step load change within the range of 10 % to 90 % of full load within 50 ms, per Telcordia
GR-947-CORE, the maximum voltage transient will not exceed 5 % of the initial steady state voltage
within 50±10 us. Recovery to within 1 % of the initial steady state voltage does not exceed 1
milliseconds.
8.
Filtering:
a)
Voice Band Noise:
Peak-peak voltage i
s ≤200 mV at 0 MHZ to 20 MHZ and normal output
voltage.
b)
Wide Band Noise:
Wideband noise voltage is
≤
50 mV at 3.4 kHz to 150 kHz and
≤
20 mV at 0.15
MHz to 30 MHz.
AC Input Ratings
1.
Voltage:
Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC / 240 VAC, single phase, 3-wire, 50 Hz
/ 60 Hz, with an operating range of 85 VAC to 300 VAC. Acceptable input frequency range is 45 Hz
to 65 Hz.
Permitted Variation:
85 VAC to 300 VAC.
2.
Harmonic Content (THD):
Meets EN61000-3-
2. ≤5 % from 50 % to 100 % of
rated output current
at 220 VAC.
3.
Inrush Current:
Peak does not exceed 1.5 times of the peak value of the maximum steady-state
input current at full load, 220 VAC input voltage, and for any duration of AC input interrupts. Under
the above conditions, standard AC distribution circuit breakers will not trip.
4.
Typical Input Data:
50 Hz input.
a) Refer to Table 2.
b)
Maximum Input Current:
Refer to Table 3.
c)
Efficiency Curve:
Refer to Figure 4.
5.
Typical Input Data:
60 Hz input.
a) Refer to Table 4.
b)
Maximum Input Current:
Refer to Table 5.
c)
Efficiency Curve:
Refer to Figure 5 and Figure 6.
Table 2: Typical Input Data with 50 Hz Input
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.747
156.234
13.38
0.08
--
45.654
25
2.559
534.2
514.9
0.96
90.901
159.854
50
4.85
1012.9
992.3
0.9786
93.979
203.849
75
7.13
1485.3
1475.8
0.9934
94.642
269.828
100
9.503
1973.8
1962.1
0.99416
94.736
352.417
110
10.457
2170.5
2159.9
0.9951
94.543
402.201