Vertiv
|
NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA)
|
Rev. F
14
Figure 3:
Power Derating Based on Temperature
6.
Regulation:
a)
Static: Steady state regulation is ±0.6% as controlled within the rectifier for any and all
combinations of load from no load to full load, input voltage, and input frequency at a constant
ambient temperature.
b)
Dynamic: Response time ≤200 us and overshot ≤5% for load changes at 50% - 25% - 50%
and 50% - 75% - 50% at rated output current.
For any step load change within the range of 10% to 90% of full load within 50 us, per Telcordia
GR-947-CORE, the maximum voltage transient will not exceed 5% of the initial steady state voltage
within 50±10 us. Recovery to within 1% of the initial steady state voltage does not exceed 1
milliseconds.
7.
Filtering:
a)
Voice Band Noise: Peak-peak voltage is ≤200 mV at 0 MHZ to 20 MHZ and normal output voltage.
b)
Wide Band Noise: Wideband noise voltage is ≤50 mV at 3.4 kHz to 150 kHz and ≤20 mV at 0.15
MHz to 30 MHz.
c)
Discrete Noise Voltage: Discrete noise voltage is ≤5 mV at 3.4 kHz to 150 kHz, ≤3 mV at 150 kHz to
200 kHz, ≤2 mV at 200 kHz to 500 kHz, and ≤1 mV at 500 kHz to 30000 kHz.
d)
Psophometric Noise: Psophometric noise is ≤2 mV typical at 220 VAC input, 53.5 VDC output, and
30% to 90% of rated load for more than one rectifier.
AC Input Ratings
1.
Voltage: Nominal 120 VAC / 208 VAC / 220 VAC / 230 VAC / 240 VAC, single phase, 3-wire, 50 Hz / 60
Hz, with an operating range of 85 VAC to 300 VAC. Acceptable input frequency range is 45 Hz to 65
Hz.
Permitted Variation: 85 VAC to 300 VAC.
2.
Harmonic Content (THD): Meets EN61000-3-2. ≤5% from 50% to 100% of rated output current at 220
VAC.
3.
Inrush Current: Peak does not exceed 1.5 times of the peak value of the maximum steady-state input
current at full load, 220 VAC input voltage, and for any duration of AC input interrupts. Under the above
conditions, standard AC distribution circuit breakers will not trip.
0
20
40
60
80
100
120
-40
-20
0
20
40
60
80
100
%
of
Ou
tp
ut
P
ow
er
Temperature (
℃
)
Output Power vs. Temperature
at 290 Vac ≥ Vin ≥ 176 Vac