Environmental Ratings
1.
Operating Ambient Temperature Range:
a)
-40 °C (-40 °F) to +55 °C (+131 °F) with full power performance.
b)
+55 °C (+131 °F) to +75 °C (+167 °F) with derating output.
c)
Temperature Coefficient: 0.02% per degrees Celsius.
2.
Storage Ambient Temperature Range: -40 °C (-40 °F) to +70 °C (+158 °F).
3.
Relative Humidity: This rectifier is capable of operating in an ambient relative humidity range of 5% to
100%.
4.
Altitude: -200 feet (- 61 m) to 13000 feet (3900 m).
5.
Surge Protection: EN61000-4-5 up to level 4, Telcordia GR-1089-Core, IEEE C62.41-2002,
YD/T 731-2002.
Performance Criteria B.
AC Power Terminals
Test Level
Source
Impedance
Performance
Criteria
Line to Line
Line to Ground
± 4 kV
± 4 kV
2 ohms
B
NA
± 6 kV
12 ohms
B
DC Power Terminals:
Test Level
Source
Impedance
Performance
Criteria
Line to Line
Line to Ground
± 500 V
± 500 V
2 ohms
B
± 800 V
± 800 V
2 ohms
B
The test method is described in EN 61000-4-5. In this test the
DC-cables shall be 5 m long.
6.
High Voltage Category (per UL60950): III
7.
Power Distribution System: TN/TT/IT
8.
EMI/RFI Suppression:
a)
The rectifier conforms to the requirements of FCC rules Part 15, Class B for radiated and conducted
emissions limits.
b)
The rectifier conforms to the requirements of European Norm, EN55022, Class B for radiated and
conducted emissions limits.