Vertiv
|
NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA)
|
Rev. F
15
4.
Typical Input Data: 50 Hz input.
a)
b)
Maximum Input Current: Refer to
c)
5.
Typical Input Data: 60 Hz input.
a)
b)
Maximum Input Current: Refer to
c)
Table 4:
Typical Input Data with 50 Hz Input
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
208
0
0.286
55.84
4.73
0.10023
--
16.137
25
1.26
258.754
245.374
0.94857
90.79
77.1101
50
2.34
485.81
479.14
0.98624
94.33
92.6646
75
3.489
725.77
721.56
0.99407
94.81
127.7476
100
4.66
970.24
967.15
0.99682
94.76
172.9354
110
5.01
1041.68
1038.95
0.99725
94.70
187.9968
240
0
0.33
73.4
4.908
0.06636
--
16.745
25
1.12
265.36
244.52
0.92218
91.16
73.7573
50
2.02
482.99
477.956
0.98977
94.59
88.2566
75
3.015
724.2
719.46
0.99357
95.10
120.301
100
4.033
969.3
966.68
0.99727
95.09
161.8856
110
4.32
1037.32
1035.1
0.99778
95.05
174.7991
Note:
System output is initially adjusted to 54 volts DC as measured at the system sense point
at 50% of full load and nominal input. “Percent of Full Load” refers to percent of 17.24
amperes.
Table 5:
Maximum Input Current with 50 Hz Input
Nominal
Input Voltage
Input
Voltage
Input Current
(Amperes)
208/240
176
7.5
Note:
At 100% of full load with output adjusted to 58 volts
DC as measured at the output terminals.