INITIALLY STARTING AND CHECKING RECTIFIER
OPERATION
Initially Starting the Rectifier
Procedure
CAUTION!
Spec. No. 561665 (R48-1000C-5) includes an internal output circuit breaker. This circuit
breaker is shipped in the “ON” position. See
1.
Apply rectifier AC input power to the system by closing the external AC disconnect or protective device.
The rectifier automatically starts.
Figure 25:
Circuit Breaker, Spec. No. 561665 (R48-1000C-5)r
Checking System Status
DANGER!
Hazardous voltages are exposed when the cover is opened and power is applied to the
product.
Procedure
1.
Observe the status of the rectifier’s local indicators. If operating normally, the status of these is as
shown in
2.
Ensure the front door is securely closed and the screws are torqued to 29 Kgf cm (2.9 Nm) (25 in-lbs).
Table 8:
Status and Alarm Indicators
Indicator
Normal State
Power (Green)
On
Protection (Yellow)
Off
Alarm (Red)
Off
Location of Circuit Breaker
(P/N 561665 Only)
This circuit breaker is
shipped in the “ON”
position.