Vertiv
|
NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA)
|
Rev. F
9
INTRODUCTION
The NetSure™ IPE SERIES provides a rectifier mounted inside an environmentally protective enclosure. The
NetSure™ IPE SERIES rectifier can be wall or pole mounted.
Ordering Structure
Configurations
The NetSure™ IPE SERIES rectifier can be provided in three (3) configurations.
•
Bulk Output : Spec. No. 561664 (R48-1000C-4).
•
Output Fed through an Internal 30 A Circuit Breaker:
Spec. No. 561665 (R48-1000C-5).
•
Output Fed through an Internal 6-Position GMT Fuse Block: Spec. No. 561666 (R48-1000C-6).
Circuit Breaker Option
Spec. No. 561665 (R48-1000C-5): A 30 A internal circuit breaker is provided.
GMT Fuse Option
Spec. No. 561666 (R48-1000C-6): An internal 6-position GMT fuse block is provided.
Specify fuses from
•
Maximum GMT fuse size is 10 A.
•
At +65 °C (+149 °F), a space is required between GMT fuses greater than 5 A.
•
When used for power distribution, load should not exceed 80% of device rating, except 10 A fuses, for
which load should not exceed 70% of device rating.
Table 1:
GMT Fuses
Ampere Rating
Part Number
Fuse Color
1/4
248610200
Violet
1/2
248610300
Red
3/4
248610500
Brown
1-1/3
248610700
White
2
248610800
Orange
3
248610900
Blue
5
248611000
Green
7-1/2
248611300
Black-White
10
248611200
Red-White