Vertiv
|
NetSure™ IPE SERIES Rectifier Installation & User Manual (UM1R481000CNA)
|
Rev. F
34
Figure 20:
Customer Wiring to the Mating Connector P/N 14190609 (-48 VDC GMT Output Connector)
(Mates to Connector Labeled Z in
Sealing cable adapter provided.
Maximum cable diameter is 6.1 mm to 8.1 mm
(0.24” to 0.32”)”.
Insert provided plug into any empty cable hole.
The following are some cable choices that fit this
connector:
General Cable HF312 Carolprene SJ00W, 16/2,
300V
Belden Waterdog 5240U1 (2/C) 16AWG, 300V
Note: Cable choices should be based on the envi-
ronment that the power system is located as well as
any National Electrical Code and local regulations.
Choices above are just examples of cables that will
fit.
Dust
Cap
Connector
Housing
Sleeve
Sealing
Cable
Adapter
Rear
Pressing
Nut
P/N 14190609
(-48 VDC GMT Fuse Output)
3+
4+
4-
1+
1-
2+
3-
2-
3+
4+
4-
1+
1-
2+
3-
2-
-48 VDC OUTPUT 1
Load 1: Return to terminal 1+, -48 VDC to terminal 1-.
Load 2: Return to terminal 3+, -48 VDC to terminal 3-.
Load 3: Return to terminal 4+, -48 VDC to terminal 4-.
-48 VDC OUTPUT 2
Load 4: Return to terminal 1+, -48 VDC to terminal 1-.
Load 5: Return to terminal 3+, -48 VDC to terminal 3-.
Load 6: Return to terminal 4+, -48 VDC to terminal 4-.
Pins for wire connections.
Accepts wires in the range
of 22 AWG to 16 AWG.
NOTE! If the sleeve and sealing cable adapter housing
are not separated before installing the cable, the cable
may twist inside the connector housing as the sleeve is
tightened to the connector housing. Perform these steps
in the correct order to prevent this from happening.
1. Strip 7.5 ± 0.5 mm (0.3 ± 0.02 inch)
of insulation off the wires.
2. With the dust cap installed, unscrew the sleeve from
the connector housing to expose the wiring terminals.
3. Remove the rear pressing nut.
4. Separate the sleeve from the sealing cable adapter
housing.
5. Slide the cable(s) through the rear pressing nut,
then through the appropriate opening(s) in the
sealing cable adapter installed in the sealing cable
adapter housing, and finally through the sleeve.
NOTE: If multiple sealing cable adapters are
furnished, select and install the appropriate sealing
cable adapter.
6. Slide the appropriate wires into the appropriate pins
of the connector housing. Tighten the screw in the
connector housing to secure the wire.
Torque to 0.8 N m (7 in-lbs).
7. Tighten the sleeve to the connector housing.
8. Slide the sealing cable adapter housing into the
sleeve.
9. Tighten the rear pressing nut to the sleeve.
Torque to 6.5 N m (58 in-lbs).
Sealing
Cable
Adapter
Housing