Figure 17:
Customer Wiring to the Mating Connector P/N 14190611 (Alarm Connector)
(Mates to Connector Labeled Y in
to
Sealing
Cable
Adapter
P/N 14190611 (Alarm Cable)
Dust
Cap
Connector
Housing
Sleeve
Rear
Pressing
Nut
Sealing
Cable
Adapter
Housing
NOTE! If the sleeve and sealing cable adapter housing
are not separated before installing the cable, the cable
may twist inside the connector housing as the sleeve is
tightened to the connector housing. Perform these steps
in the correct order to prevent this from happening.
1. Strip 7.5 ± 0.5 mm (0.3 ± 0.02 inch)
of insulation off the wires.
2. With the dust cap installed, unscrew the sleeve from
the connector housing to expose the wiring terminals.
3. Remove the rear pressing nut.
4. Separate the sleeve from the sealing cable adapter
housing.
5. Slide the cable(s) through the rear pressing nut,
then through the appropriate opening(s) in the
sealing cable adapter installed in the sealing cable
adapter housing, and finally through the sleeve.
NOTE: If multiple sealing cable adapters are
furnished, select and install the appropriate sealing
cable adapter.
6. Slide the appropriate wires into the appropriate pins
of the connector housing. Tighten the screw in the
connector housing to secure the wire.
Torque to 0.8 N m (7 in-lbs).
7. Tighten the sleeve to the connector housing.
8. Slide the sealing cable adapter housing into the
sleeve.
9. Tighten the rear pressing nut to the sleeve.
Torque to 6.5 N m (58 in-lbs).
Sealing cable adapter provided.
Maximum cable diameter is 6.1 mm to 8.1
mm (0.24” to 0.32”).
Insert provided plug into any empty cable
hole. If this connector is not used, place
dust cap onto connector.
The following are some cable choices that
fit this connector:
Alarm Contact Cabling:
Belden Waterdog 5504G1 (6/C) 22AWG,
300V
CAN Bus Cabling:
Belden Waterdog 5502G1 (4/C) 22AWG,
300V
Note: Cable choices should be based on
the environment that the power system is
located as well as any National Electrical
Code and local regulations. Choices
above are just examples of cables that will
fit.
3
4
5
1
8
2
6
7
Rectifier Fail to terminals 1 and 2.
AC Fail to terminals 3 and 4.
Fuse or Circuir Breaker Alarm to
terminals 7 and 8 (if available).
CAN_H to terminal 5.
CAN_L to terminal 6.
ALARM
Pins for wire connections.
Accepts 22 AWG wires maximum.