SAG582140600
System Application Guide
Revision E, November 15, 2018
Spec. No. 582140600 (Model 8100
DB
)
Page 10 of 67
LIST DESCRIPTIONS (582140600)
List Numbers
582140600 List 01: Common Equipment, 6-Panel Bay, 30” W x 16” D x 84” H
Features
♦
List 01 provides the common equipment for a 6-distribution panel BDF/CBB (Battery Distribution Fuse/Circuit Breaker
Bay).
♦
Configurable for top or bottom feed.
♦
Consists of a 30” W x 16” D x 84” H welded box framework (seismic, zone 4 earthquake compliant).
♦
Includes Monitor Unit Model M832DNA.
♦
Includes an IB4 board (second Ethernet port for the monitor unit). The Ethernet port located on the monitor unit can be
used to connect a computer directly to the monitor unit. The Ethernet port located on the IB4 board can be used to
connect the monitor unit to your Local Area Network (LAN).
♦
Includes connection points for four (4) fused auxiliary -48V power outputs (1-1/3A) and fused remote (A/B) electronics
inputs.
Restrictions
You can vertical parallel along with side by side parallel but the limitation is that you can use only one (1) of P/N 563497 per
set of panels tied together and it must be installed on the bottom set of panels of the set in a top feed and top set of panels of
the set on a bottom feed.
Ordering Notes
1)
Order up to six (6) Lists 20 (see page 17), List 25 (see page 17), and/or List 25A (see page 18) distribution panels per bay.
a)
Order fuses and/or circuit breakers as required per “Distribution Devices and Lug Selection” on page 31.
b)
Order load distribution lugs as required per “Distribution Devices and Lug Selection” on page 31.
c)
For load and load return lug-mounting hardware, order load lug hardware kits (ship-loose) (see page 23) as required,
or order List 67 (pre-installed) (see page 22).
d)
For any open distribution panel position, order a List 28 blank panel (see page 19.
2)
If distribution panels (per side) are to be paralleled, order a List 30 distribution panel paralleling bar (see page 20). Each
List 30 includes two (2) paralleling bars (one per side).
3)
If distribution panels (side by side) are to be paralleled, order P/N 563497 distribution panel paralleling bar (see page 23).
4)
Order List 43 input feed and shunt assembly as required (see page 20). Each List 43 provides input terminations and
shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 43 and specify top or bottom feed.
For top and bottom feed multi-load applications, order three (3) List 43 for each side A / side B load and specify top or
bottom feed.
List 20 Only: For 3-load side by side applications, order three (3) List 43, and order three (3) P/N 563497.
List 25 and List 25A Only: For 3-load side by side applications, order three (3) List 43, and order three (3) P/N 563497.
5)
Order DC input lugs as required (see “DC Input Connections” on page 54).
6)
Order bay frame grounding lugs as required (see page “Bay Frame Grounding Requirements” on page 41).
7)
Order List 26 (see page 18) or List 27 (see page 19) internal ground bars as required, or use external ground bars as
required (see page 28).
8)
List 26 provides input lug landing points at the top or bottom (as specified) of the full bay length ground/return busbars.
List 26 internal return bars are rated for 1200 A. List 48 (see page 21) is available to increase that capacity to 2400 A
and provide additional cable landing points. Each bay can accommodate (1) List 48. List 48 offers cable termination at
the rear of the bay and the option of a bonding strap.
9)
Order List 51 cable dressing bars (see page 21) or List 53 load distribution cable management kit (see page 22) as
required.
10)
Order List 54 top cover (see page 22) as required.
11)
Order TVSS device(s) as required (see page 30).