System Application Guide
SAG582140600
Spec. No. 582140600 (Model 8100
DB
)
Revision E, November 15, 2018
Page 17 of 67
582140600 List 20: TLS/TPS Fuse and/or TPL-B Fuse Distribution Panel, 6-Panel Bay
Features
♦
Twenty (20) TLS/TPS fuse positions, or ten (10) TPL-B fuse positions, or a combination of
TLS/TPS and TPL-B fuse positions.
♦
Includes twenty (20) TLS/TPS fuseholders P/N 248817100. For panels factory configured in
a bay, each TPL-B fuseholder P/N 516241 ordered replaces two (2) P/N 248817100
fuseholders.
♦
See “Load Distribution Connections” starting on page 44 for load termination specifications.
♦
Distribution panel is monitored for load voltage, load current, and fuse / circuit breaker alarm
status per panel.
Restrictions
640 A maximum continuous.
For use in List 01 and List 03.
Ordering Notes
1)
Order as required.
2)
Specify twenty (20) TLS/TPS fuseholders, or up to ten (10) TPL-B fuseholders, or a
combination per distribution panel (all positions MUST be filled). This instructs the factory
how to configure the distribution panel. Also specify mounting location for each configured
distribution panel per bay. This instructs the factory where to mount each configured
distribution panel per bay.
3)
Order fuses and lugs as required per “Distribution Devices and Lug Selection” on page 31.
4)
Replacement panels will be equipped with twenty (20) TLS/TPS fuseholders. TPL-B fuseholders (P/N 516241) may be
ordered to field modify the distribution panel. One (1) TPL-B fuseholder takes the space of two (2) TLS/TPS fuseholders.
582140600 List 25: Bullet Breaker and/or TLS/TPS Fuse Distribution Panel, 6-Panel Bay
Features
♦
Twenty-eight (28) bullet nose circuit breaker and/or TLS/TPS fuse (with bullet nose
fuseholder) positions.
♦
See “Load Distribution Connections” starting on page 44 for load termination
specifications.
♦
Distribution panel is monitored for load voltage, load current, and fuse / circuit breaker
alarm status per panel.
Restrictions
640 A maximum continuous.
For use in List 01 and List 03.
Ordering Notes
1)
Order as required.
2)
Specify mounting location for each distribution panel per bay. This instructs the factory
where to mount each distribution panel when the bay is populated with different types of
distribution panels.
3)
Order distribution fuses, fuseholders, circuit breakers, and load lugs as required per
“Distribution Devices and Lug Selection” on page 31.