System Application Guide
SAG582140600
Spec. No. 582140600 (Model 8100
DB
)
Revision E, November 15, 2018
Page 49 of 67
Figure 16 (cont'd from previous page, cont'd on next page)
Load Distribution Connections
Bullet Device Mounting Block
DANGER
TPL-B Fuseblock
5/16-18 swage studs
for installation of customer
provided single hole lugs.
(Torque to 132 in-lbs.)
(Maximum Lug Width is 1.800”.)
(Maximum Wire Size is 2/0 AWG.)
TLS/TPS Fuseblock
1/4-20 swage studs
for installation of customer
provided single hole lugs.
(Torque to 72 in-lbs.)
(Maximum Lug Width is 0.750”.)
(Maximum Wire Size is 2 AWG.)
-48V Load
Connections
-48V Load
Connections
1/4-20 studs on 5/8” centers
for installation of customer
provided two hole lugs.
(Torque to 72 in-lbs.)
(Maximum Lug Width is 0.610”.)
(Maximum Wire Size is 2 AWG.)
-48V Load
Connections*
or
TVSS
Connections
(+Ground)*
Ensure leads are connected to
proper polarity for the device
installed, either a Distribution
Device (load lead connection)
or a TVSS Device (ground
connection).
*
-48V Load
Connections*
or
TVSS
Connections
(+Ground)*
-48 VDC Load Connections and
TVSS Device Ground Connections to
List 15, List 15A, List 25, and List 25A Distribution Panel
-48 VDC Load Connections to
List 10 and List 20 Distribution Panel
Rear View
(wired from the rear of the bay)
Rear View
(wired from the rear of the bay)
List 15
(List 25 Similiar)
List 15A
(List 25A Similiar)
List 10
(List 20 Similiar)
List 10
(List 20 Similiar)