SAG582140600
System Application Guide
Revision E, November 15, 2018
Spec. No. 582140600 (Model 8100
DB
)
Page 46 of 67
Fuse/
Circuit
Breaker
Amperage
Recm 90
°
C Wire Size
(1)
4 AWG
2 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
350 kcmil
Loop Length (feet)
(2)
90A
41
(3)
66
(3, 4)
105
(3, 4)
133
(4)
--
--
--
--
100A
--
59
(3, 4)
95
(3, 4)
119
(3, 4)
--
--
--
--
125A
--
47
(3)
76
(3, 4)
95
(3, 4)
120
(4)
--
--
--
150A
--
--
63
(3, 4)
79
(3, 4)
100
(3, 4)
--
--
--
175A
--
--
--
68
(3, 4)
86
(3, 4)
108
(3, 4)
--
--
200A
--
--
--
--
75
(3, 4)
95
(3, 4)
112
(3, 4)
--
225A
--
--
--
--
67
(3)
84
(3, 4)
100
(3, 4)
--
250A
--
--
--
--
--
76
(3, 4,
7)
90
(3, 4,
7)
126
(3, 4,
7)
300A
--
--
--
--
--
--
--
105
(3, 4,
7)
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved National Fire
Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for copper wire at 90 °C conductor
temperature. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for the loop
lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30 °C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40 °C Ambient Operating Temperature.
Table 16 (cont'd from previous page)
Recommended Load Distribution Wire Sizes for
TLS/TPS Fuse and Bullet Nose-Type Circuit Breaker