SAG582140600
System Application Guide
Revision E, November 15, 2018
Spec. No. 582140600 (Model 8100
DB
)
Page 18 of 67
582140600 List 25A: Advanced Bullet Breaker and/or TLS/TPS Fuse Distribution Panel with Individual Current
Monitoring, 6-Panel Bay
Features
♦
Twenty-eight (28) bullet nose circuit breaker and/or TLS/TPS fuse (with bullet nose
fuseholder) positions with advanced monitoring.
♦
Individual circuit breaker and/or TLS/TPS fuse current monitoring including; Power,
Energy, and FA/CB alarm per position.
♦
See “Load Distribution Connections” starting on page 44 for load termination
specifications.
♦
Distribution panel is monitored for load voltage, load current, and fuse / circuit breaker
alarm status per panel and per distribution device.
Restrictions
640 A maximum continuous.
For use in List 01 and List 03.
Ordering Notes
1)
Order as required.
2)
Specify mounting location for each distribution panel per bay. This instructs the factory
where to mount each distribution panel when the bay is populated with different types of
distribution panels.
3)
Order distribution fuses, fuseholders, circuit breakers, and load lugs as required per
“Distribution Devices and Lug Selection” on page 31.
582140600 List 26: Optional Internal Ground/Return Bar, 6-Panel Bay (Full Bay Length)
Features
♦
Provides two (2) full bay length internal ground/return bars (one per side).
♦
See “Load Distribution Connections” starting on page 44 for load termination specifications.
♦
Includes two (2) input lug landing plate assemblies (one per side).
♦
Can be configured for top or bottom feed.
Restrictions
For use in List 01 and List 03.
Ordering Notes
1)
Order as required.
2)
Specify mounting location of included input lug landing plate assemblies: Top for top-feed or bottom for
bottom feed.
3)
List 26 internal ground/return bars are rated for 1200 A. List 48 is available to increase that capacity to
2400 A and provide additional cable landing points. Each bay can accommodate one (1) List 48. List 48
offers cable termination at the rear of the bay and the option of a bonding strap. Mounting location (top
or bottom) of List 48 will be opposite that specified for the input lug landing plate assemblies of List 26.
4)
Order load lugs as required per “Distribution Devices and Lug Selection” on page 31.