System Application Guide
SAG582140600
Spec. No. 582140600 (Model 8100
DB
)
Revision E, November 15, 2018
Page 13 of 67
582140600 List 09: Common Equipment, 8-Panel Bay, 30” W x 24” D x 84” H
Features
♦
List 09 provides the common equipment for a 8-distribution panel BDF/CBB (Battery Distribution Fuse/Circuit Breaker
Bay).
♦
Configurable for top or bottom feed.
♦
Consists of a 30” W x 24” D x 84” H welded box framework (seismic, zone 4 earthquake compliant).
♦
Includes Monitor Unit Model M832DNA.
♦
Includes an IB4 board (second Ethernet port for the monitor unit). The Ethernet port located on the monitor unit can be
used to connect a computer directly to the monitor unit. The Ethernet port located on the IB4 board can be used to
connect the monitor unit to your Local Area Network (LAN).
♦
Includes connection points for four (4) fused auxiliary -48V power outputs (1-1/3A) and fused remote (A/B) electronics
inputs.
Restrictions
You can vertical parallel along with side by side parallel but the limitation is that you can use only one (1) of P/N 563497 per
set of panels tied together and it must be installed on the bottom set of panels of the set in a top feed and top set of panels of
the set on a bottom feed.
Ordering Notes
1)
Order up to eight (8) Lists 10 (see page 14), List 15 (see page 14), and/or List 15A (see page 15) distribution panels per
bay.
a)
Order fuses and/or circuit breakers as required per “Distribution Devices and Lug Selection” on page 31.
b)
Order load distribution lugs as required per “Distribution Devices and Lug Selection” on page 31.
c)
For load and load return lug-mounting hardware, order load lug hardware kits (ship-loose) (see page 23) as required,
or order List 67 (pre-installed) (see page 22).
d)
For any open distribution panel position, order a List 28 blank panel (see page 19.
2)
If distribution panels (per side) are to be paralleled, order a List 31 distribution panel paralleling bar (see page 20). Each
List 31 includes two (2) paralleling bars (one per side).
3)
If distribution panels (side by side) are to be paralleled, order P/N 563497 distribution panel paralleling bar (see page 23).
4)
Order List 43 input feed and shunt assembly as required (see page 20). Each List 43 provides input terminations and
shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 43 and specify top or bottom feed.
For top and bottom feed multi-load applications, order two (2) or four (4) List 43 for each Side A/Side B load and specify
top or bottom feed. Order List 31 as required.
List 10 Only: For 4-load side by side applications, order four (4) List 43, and order four (4) P/N 563497. For top and
bottom feed 2-load side by side applications, order two (2) List 43, two (2) P/N 563497, and two (2) List 31.
List 15 and 15A Only: For 4-load side by side applications, order four (4) List 43, and order four (4) 563497. For top and
bottom feed 2-load side by side applications, order two (2) List 43, two (2) 563497, and two (2) List 31.
5)
Order DC input lugs as required (see “DC Input Connections” on page 54).
6)
Order bay frame grounding lugs as required (see page “Bay Frame Grounding Requirements” on page 41).
7)
Order List 16 (see page 15) or List 17 (see page 16) internal ground bars as required, or use external ground bars as
required (see page 28).
8)
List 16 provides input lug landing points at the top or bottom (as specified) of the full bay length ground/return busbars.
List 16 internal return bars are rated for 1200 A. List 48 (see page 21) is available to increase that capacity to 2400 A and
provide additional cable landing points. Each bay can accommodate (1) List 48. List 48 offers cable termination at the
rear of the bay and the option of a bonding strap.
9)
Order List 52 cable dressing bars (see page 21) or List 53 load distribution cable management kit (see page 22) as
required.
10)
Order List 55 top cover (see page 22) as required.
11)
Order TVSS device(s) as required (see page 30).