SAG582140600
System Application Guide
Revision E, November 15, 2018
Spec. No. 582140600 (Model 8100
DB
)
Page 14 of 67
582140600 List 10: TLS/TPS Fuse and/or TPL-B Fuse Distribution Panel, 8-Panel Bay
Features
♦
Twelve (12) TLS/TPS fuse positions, or six (6) TPL-B fuse positions, or a combination
of TLS/TPS and TPL-B fuse positions.
♦
Includes twelve (12) TLS/TPS fuseholders P/N 248817100. For panels factory
configured in a bay, each TPL-B fuseholder P/N 516241 ordered replaces two (2) P/N
248817100 fuseholders.
♦
See “Load Distribution Connections” starting on page 44 for load termination
specifications.
♦
Distribution panel is monitored for load voltage, load current, and fuse alarm status
per panel.
Restrictions
640 A maximum continuous.
For use in List 07 and List 09.
Ordering Notes
1)
Order as required.
2)
Specify up to twelve (12) TLS/TPS fuseholders, or up to six (6) TPL-B fuseholders, or a combination per distribution
panel (all positions MUST be filled). This instructs the factory how to configure the distribution panel. Also specify
mounting location for each configured distribution panel per bay. This instructs the factory where to mount each
configured distribution panel per bay.
3)
Order fuses and lugs as required per “Distribution Devices and Lug Selection” on page 31.
4)
Replacement panels will be equipped with twelve (12) TLS/TPS fuseholders. TPL-B fuseholders (P/N 516241) may be
ordered to field modify the distribution panel. One (1) TPL-B fuseholder takes the space of two (2) TLS/TPS fuseholders.
582140600 List 15: Bullet Breaker and/or TLS/TPS Fuse Distribution Panel, 8-Panel Bay
Features
♦
Sixteen (16) bullet nose circuit breaker and/or TLS/TPS fuse (with bullet nose
fuseholder) positions.
♦
See “Load Distribution Connections” starting on page 44 for load termination
specifications.
♦
Distribution panel is monitored for load voltage, load current, and fuse / circuit
breaker alarm status per panel.
Restrictions
640 A maximum continuous.
For use in List 07 and List 09.
Ordering Notes
1)
Order as required.
2)
Specify mounting location for each distribution panel per bay. This instructs the
factory where to mount each distribution panel when the bay is populated with
different types of distribution panels.
3)
Order distribution fuses, fuseholders, circuit breakers, and load lugs as required per
“Distribution Devices and Lug Selection” on page 31.