background image

I.L.  41-600.7 

O

P

E

R

A

T

 

O

N

  O

F

  S

C

H

E

M

E

 

INSTRUCTIONS 

WESTINGHOUSE  TYPE  HKB  SINGLE  POLE 

CARRIER  RELAYING  AND  RECLOSING 

GENERAL 

This 

scheme 

provides 

single  pole  tripping 

and 

reclosing  for  phase  to  ground  faults,  and 

three 

pole  tripping  and 

reclosing  (optional) 

for  phase  faults 

including  two  line  to  ground 

faults. 

This  is,  for  all  internal  phase  A-to­

ground 

faults,  only 

the  phase  A  pole  of  the 

circuit  breakers  of  both  ends  of  the  protected 
line  will  be 

opened. 

In  a  like  manner,  only 

phase  B  pole  will  be  operated  for  phase  B-to­

ground  faults  and  only  phase  C  pole  for  phase 

C-to-ground  faults. 

For  each  of  these  faults 

the  opened  pole  will  be  reclosed  immed·iately 
at  each  end. 

On 

any  internal  three-phase,  phase-to-phase, 

or  two-phase-to-ground 

fault  all  three  poles 

of  the  circuit 

breaker 

will  be  opened. 

Im­

mediate  reclosing  for  these  faults  is  op­

tional,  that  is,  three  pole  reclosing  can  be 
provided 

if  desired  or 

three  pole 

reclosing 

can  be  blocked. 

The  back-up  relays  used 

to  supplement  the 

type 

HKB 

Single  pole  carrier  relays  provide  a 

separate  independent  protective  system, 

These 

back-up  relays  trip  all  three  poles  and  may  be 

directional 

overcurrent, 

d irectional 

im­

pedance, 

etc. 

If  the  types  .HZ  Impedance  or 

HZM  distance  relays  and 

instantaneous  trip 

attachments  are  used,  then  a  time  delay  relay 

is  necessary  to  d elay  the  instantaneous  back­
up  relays  from  tripping  all  three  poles  until 
the  carrier  relays  have  had  an  opportunity  to 

trip  single  pole. 

COMPONENTS  OF 

COMPLETE  EQUIPMENT 

The  relay 

components  of  the  type 

HKB 

Single 

pole  carrier  system  consis�s  of  the  following: 

1  Type 

HKB 

Carrier  Relay  and  Auxiliaries 

1  Type  H�S  Phase  Selector  Relay 

1  Type  .HZM-3  Distance  Relay 

Type  SGR-12  Reclosing  Relays  as  Req. 

as  Req.  Type 

SG 

and  MG  Auxiliary  Relays 

NEW  INFORMATION 

This  list  does  not  include  phase  and  ground 

back-up  relays  which 

provide  an  ind ependent 

relay  system. 

OPERATION 

The  schematic  connections  for  a  typical  type 

HKB 

single  pole  system  is  shown  in 

figs. 

3  to  6 

• 

The  type 

HKB 

relay  itself  operates 

in  the  same  manner  as  described 

in 

I.L. 

41-

600.3. 

The  common  tripping  contacts  of  this 

relay  are  supervised  by  the  types 

HQS 

and  HZM-

relays  as  sho•,rn  on 

in 

figure 

unrl.er 

"Carrier  Trip  Circuits". 

These 

relays  have 

the  following  operating  characteristics : 

The  type  HQS  phase  selector  relay 

is  con­

nected 

to  receiver 

negative  sequence  current 

from  a 

three-phase 

negative  sequence  filter 

energized 

by  the  current  transformers  and  the 

residual  current  from  the  neutral  circuit  of 

the  current  transformers. 

On  all  single  line­

to-ground  faults,  the  zero  sequence  components 

of  all  three 

phases  are  essentially  in  phase 

with  the  negative  sequence  component  of  the 
faulted 

phase. 

This  means  on  a  phase-A-to­

ground 

fault,  for  example,  the  phase  A  phase 

selector 

element  will  have 

contact  closing 

torque  while  the  phase  B  and  C  elements  will 

have  contact-opening  torque,  since  the  B  and  C 

components  of  negative 

essentially  120° 

out  of 

tive  sequence  component 

phase. 

sequence  current  are 

phase  with  the  nega­

of  the 

unfaulted 

On 

all  double  line--to-ground-faults, 

the 

three  zero  sequence  components  are  essentially 
in  phase  with  the  negative  sequence  component 

of  the  unfaulted  phase, 

For  example,  consider 

a  phase  B-C  to-ground  fault. 

In  this  case  the 

phase 

phase  selector  element  will  receive 

contact  .closing  torque  while  the  phase  B  and  C 
elements 

will 

not, 

because 

the  negative 

sequence 

components  of  these  two  phases  are 

EFFECTIVE  JANUARY  1949 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание HKB

Страница 1: ... Relay 3 Type SGR 12 Reclosing Relays as Req as Req Type SG and MG Auxiliary Relays NEW INFORMATION This list does not include phase and ground back up relays which provide an independent relay system OPERATION The schematic connections for a typical type HKB single pole system is shown in figs 3 to 6 The type HKB relay itself operates in the same manner as described in I L 41 600 3 The common tri...

Страница 2: ...ground faults than for 2 X X Fig 2 0perating Characteristics of the Type HZM 3 Relay on Single Line to Ground Faults plotted on an a X Diagram phase faults On phase faults the delta relay voltage is almost completely collapsed as compared to a collapse of not more than 57 for ground faults Thus for heavy close in ground faults the impedance seen by the relay will be outside the relay setting The t...

Страница 3: ... For I L 41 600 7 a phasc pole the A to ground fault which trips phase A high speed breaker switch 52bb will close to immediately reclose this pole The breaker auxiliary closing relay closes its contact 52X to energize 79X 0 coil This is the operating coil of the toggle element in the type SGR 12 reclosing relay Contact 79X in the closing circuit is thus opened to pre vent further reclosing of pol...

Страница 4: ...g out reclosure of all three breaker poles This b switch which energizes the SGF relay must be set so that it never closes on a 4 STATION 8us 5 r 3 I t 3 t 1Nr ON f rru ff li Z Z 1 t _ s 8 X 10 H 11 X _ X 15 16 1 7 1 19 Z O CAA IItlflt SIIoii TUI 1E 3 TE 5T RI 115 1 fba TE ST SOURO 1N HC T M QUS TRIP H Etl SOPPI Ii tl Fiq 3 Typical Carrier Control and Alarm Circuits for the Type HKB Sinqle Pole Ca...

Страница 5: ...aker contacts are not l l 41 600 7 fUlly opened but are parted sufficiently to extinguish the arco Correspondingly the breaker auxiliary switch is not completely operated J Fig 4 Typical Reclosing Circuits for the Type HKB Single Pole Carrier Relaying Scheme 5 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 6: ... C 71 1 8 SU 5 1 SGR H 9 I 361 524 J f II 7 IZ H f n _____________ 1 f t i M 3111 D UG l lisu Sl sGJ s r t c o o f r 7 t SA liS C J S ISO ici C 3XO 52V LOW f ltESSURE Fiq 5 Typical Reclos ng Circuits for the Type HKB Single Pole Carrier Relaying Scheme 6 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 7: ... CONTACT C L OSED lUG CAli RJER Tt T SLEET CARRIQ C JTfiBQL C RCUJIS CONNECT TO TCl MIHAL 7 f C 411 RICR SCT 1 0 Z 50 4C ONJ Y Fig 6 Typical Carrier Control and Alarm Circuits for the Type HKB Single Pole Carrier Relaying Scheme 7 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 8: ...WESTINGHOUSE ELECTR IC CORPORATION METER DIVISION e NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: