Westinghouse HKB Скачать руководство пользователя страница 3

HKB  SINGLE  POLE 

The  back-up  relays  either  phase  or  ground 

trip  all  three  poles  of  the  breaker  for  all 
types  of  faults  within  their  range. 

These 

relays  energize  the  type  MG  relay  (designated 

MGT

which  in  turn  trips  the  three  phase 

poles. 

The  instantaneous  elements  of 

the 

back-up 

relays  are  connected 

thru  the  type 

TG-1  Time  Delay  relay. 

This  relay  has  a  time 

setting  of  5  to  15  cycles  after  which  it 
energized 

MGT 

coil  to  trip 

all 

1:hree  poles. 

This  time  delay  prcrvldes  an  opportunity  for 
the  carrier  relays  to  trip  one  pole  if  the 
fault  is  single  line  to  ground. 

When  carrier 

single  pole  relaying  is  out  of  service,  a  con­
tact  on  the  type  W  carrier  switch  shorts  out 
this  time  delay  relay. 

telephone  type  relay  designated  X3  in  the 

type  H�S  relay  is  used  to  prevent  the  unfault­
ed  trip  circuits  from  being  energized  moment­
arily  by  the  transient  response  of  the  type 
H�S  element, 

when  the  fault  current  disap­

pears. 

The  break 

contact  of 

X3 

is  connected 

in  each  of  the  three  phase-�elector  trip 
paths. 

The  X3  contact  opens  in  about  3-4 

c�cles  and  closes  instantaneously. 

This  con­

tact  does  not  open  up  the  trip  coil  current  on 
the  faulted  phase  since  this  has  been  sealed 
in  previously. 

The  X3  relay  as  well  as  the  types 

JD 

and 

SGG 

relays  are  energized  either  by  the  type 

HKB 

relay  trip  circuit  thru  the  contactor  switch 
or  when  any  one  or  two  poles  only  are  open. 

The  SGG  relay  shorts  out  the  coils  of  the 

ground  back-up  relay  type  CWC  or  CWP. 

This  is 

necessary  only 

if  the  relay  is  set  sensitively 

with  a  short  time  and  might  operate  before  the 

opened  pha�e 

is 

reclosed. 

The  type 

JD 

timing 

relay 

limits  the  time  which  the  line  can 

oe 

operated  with  one  or  two  phases  open  and  thus 
serves  a  back-up  ground  relay. 

The  operatim1  of  the  carrier  control  cir­

cuits  are  the  same  as  in  the  standard  carrier 

scheme. 

Automatic  immediate  reclosing  is  provided 

thru  high  speed  breaker  switches  after  one 
pole  of  the  breaker  is  opened,  but  if  all 
three  poles  open  immediate  reclosure  may  or 

may  not  be 
conditions. 

in  figure 

permitted  depending  upon  system 

The  reclosing  scheme  is  shown  on 

5,  and  operates  as  follows: 

For 

I.L.  41-600.7 

a  phasc; 

pole,  the 

A-to-ground  fault  which  trips  phase 

high  speed  breaker  switch 

52bb, 

will  close  to 

immediately  reclose  this  pole. 

The  breaker  auxiliary  closing  relay  closes  its 

contact 

52X  to  energize  79X-0  coil. 

This  is 

the  operating  coil  of  the  toggle  element  in 
the  type  SGR-12  reclosing  relay. 

Contact  79X 

in  the  closing  circuit  is  thus  opened  to  pre­
vent  further  reclosing  of  pole  A. 

Another 

contact  on  the  toggle  element,  79X,  is  closed 
to  en�gize  the  reset  motor  (79M)  of  the  type 
SGR-12  relay  when  the  breaker  pole  closes  as 
indicated  by  the  closing 

of  52a. 

If 

the 

breaker 

stays  closed  the  motor  contact  79M 

closes  after  a  suitablA  delay  to  energize  the 
toggle  relay  reset  coil  79X-O. 

This  coil  re­

sets  the  two  79X  contacts  which  in  turn  de­

energizes 

the  timing  motor  and  resets  the 

closing  circuit  for  a  subsequent  trip. 

A  similar 

sequence 

of  operations  will  take 

place  for  the 

are  opened  by 
relays. 

It  is 

other  breaker  poles  when  they 

operation  of  the  protected 

to  be  noted  that  the  manual 

control 

switch  and  the  back-up  relays  all 

energize  a  master  tripping  relay  MGT. 

Make 

contacts  on  MGT  operate  the  toggle  element 
79X-O  of  the  type  SGR-12  recloser  to  lock  out 
and  block  reclosure  until  after  the  breaker 

poles  are  manually  reclosed. 

Reclosing  is 

also  blocked  when  carrier  is  out  of  service  by 

the  type 

W  carrier  switch. 

If  instantaneous 

reclosing  is  to  be  prevented  for  internal 
phase  faults  tripped  by  carrier,  then  another 

type  MG  relay  is  required. 

This  relay  is 

energized  by  CSl  contactor  switch  of  the  t�e 
HZM-3  relay. 

This  type  MG  �elay  will  trip  all 

three  breaker  poles  and  energize  7�X  to  lock 

out  and  block  recloser  of  all  thrAe  breaker 
poles. 

The  manual  closing  switch,  101-C,  operates 

a  master  closing  relay  designated  MG-Cl. 

The 

contacts  of  this  relay  energize  the  closing 
circuit  of  each  of  the  three  poles. 

In  the  above 

the  breaker 

discussion  it  was  assumed  that 

poles  remained  closed  after  the 

first  reclosure  indicating  that  the  fault  was 

not  permanent. 

If  the  arc  restrikes  or  the 

fault  is 

solid,  then  the  protective  relays 

will  operate  to  retrip  the  breaker  poles 

again. 

This  time  one  or  more  of  the  79X  re­

closing  contacts  of  the  type  SGR-12  recloser 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание HKB

Страница 1: ... Relay 3 Type SGR 12 Reclosing Relays as Req as Req Type SG and MG Auxiliary Relays NEW INFORMATION This list does not include phase and ground back up relays which provide an independent relay system OPERATION The schematic connections for a typical type HKB single pole system is shown in figs 3 to 6 The type HKB relay itself operates in the same manner as described in I L 41 600 3 The common tri...

Страница 2: ...ground faults than for 2 X X Fig 2 0perating Characteristics of the Type HZM 3 Relay on Single Line to Ground Faults plotted on an a X Diagram phase faults On phase faults the delta relay voltage is almost completely collapsed as compared to a collapse of not more than 57 for ground faults Thus for heavy close in ground faults the impedance seen by the relay will be outside the relay setting The t...

Страница 3: ... For I L 41 600 7 a phasc pole the A to ground fault which trips phase A high speed breaker switch 52bb will close to immediately reclose this pole The breaker auxiliary closing relay closes its contact 52X to energize 79X 0 coil This is the operating coil of the toggle element in the type SGR 12 reclosing relay Contact 79X in the closing circuit is thus opened to pre vent further reclosing of pol...

Страница 4: ...g out reclosure of all three breaker poles This b switch which energizes the SGF relay must be set so that it never closes on a 4 STATION 8us 5 r 3 I t 3 t 1Nr ON f rru ff li Z Z 1 t _ s 8 X 10 H 11 X _ X 15 16 1 7 1 19 Z O CAA IItlflt SIIoii TUI 1E 3 TE 5T RI 115 1 fba TE ST SOURO 1N HC T M QUS TRIP H Etl SOPPI Ii tl Fiq 3 Typical Carrier Control and Alarm Circuits for the Type HKB Sinqle Pole Ca...

Страница 5: ...aker contacts are not l l 41 600 7 fUlly opened but are parted sufficiently to extinguish the arco Correspondingly the breaker auxiliary switch is not completely operated J Fig 4 Typical Reclosing Circuits for the Type HKB Single Pole Carrier Relaying Scheme 5 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 6: ... C 71 1 8 SU 5 1 SGR H 9 I 361 524 J f II 7 IZ H f n _____________ 1 f t i M 3111 D UG l lisu Sl sGJ s r t c o o f r 7 t SA liS C J S ISO ici C 3XO 52V LOW f ltESSURE Fiq 5 Typical Reclos ng Circuits for the Type HKB Single Pole Carrier Relaying Scheme 6 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 7: ... CONTACT C L OSED lUG CAli RJER Tt T SLEET CARRIQ C JTfiBQL C RCUJIS CONNECT TO TCl MIHAL 7 f C 411 RICR SCT 1 0 Z 50 4C ONJ Y Fig 6 Typical Carrier Control and Alarm Circuits for the Type HKB Single Pole Carrier Relaying Scheme 7 w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 8: ...WESTINGHOUSE ELECTR IC CORPORATION METER DIVISION e NEWARK N J Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: