10.3.1 Blower Motor Lubrication
•
Motor is lubricated at the factory and does not require initial lubrication.
•
Contact the motor manufacturer for the lubricationinterval for motor bearings that have grease fittings.
•
Contact the motor manufacturer to determine what type of grease to use for lubrication. Greases of different
bases may not be compatible whenmixed.
10.3.2 Belt Inspection
Check the drive belt monthly for signs of wear and for proper tension. Withproper care, a belt should last several years.
Replace belts that appear wornor cracked withanidentically-sized belt. Belts that are too tight cancause excessive wear.
To check belt tension:
Press the belt midway betweenthe sheave and the pulley and check for movement from 1/2 in. to 1 in. (12 mm to 25 mm). If
there is less than1/2 in. (12 mm) of movement, the belt is too tight.
10.3.3 Electronic Variable Speed Drive - Inverter
Anoptional, variable-speed drive is available. This packaged unit is factory-set and should not require field adjustment. If
yoususpect a problem withthe inverter, contact the factory.
To removing VSD from the unit:
1. Turnoff power at the unit disconnect.
2. Openthe unit accent panel and electric box cover.
3. Find the mainfanmotor wires, whichare connected to the motor overload relay inthe high-voltage sectionof
the electric box.
a. Mark motor wires to ensure they canbe reconnected inthe same order.
b. Disconnect motor wires at the load side of the motor overload relay.
c. Close the electric box cover.
4. Remove the right front vertical panel to gainaccess to the variable speed drive.
5. Withthe panel removed, restore power to the unit by turning the disconnect on.
6. Place the right front vertical panel back onthe unit.
7. Reconnect the motor wires to the overload and close the electric box cover and unit accent panel.
8. Restore power at the disconnect.
10 Maintenance
97
Содержание Liebert CW 038
Страница 14: ...Vertiv Liebert CW Installer User Guide 14 Thispageintentionally left blank...
Страница 22: ...Vertiv Liebert CW Installer User Guide 22 Thispageintentionally left blank...
Страница 38: ...Vertiv Liebert CW Installer User Guide 38 Thispageintentionally left blank...
Страница 44: ...Figure 7 2 Lowering EC fans into floor steps 8 through 9 Vertiv Liebert CW Installer User Guide 44...
Страница 80: ...Vertiv Liebert CW Installer User Guide 80 Thispageintentionally left blank...
Страница 102: ...Vertiv Liebert CW Installer User Guide 102 Thispageintentionally left blank...
Страница 105: ...2 Check contactorsfor pitting Replaceifpitted 3 Check Re torquewireconnections 11 PreventiveMaintenanceChecklist 105...
Страница 108: ...Vertiv Liebert CW Installer User Guide 108 Thispageintentionally left blank...
Страница 167: ...Vertiv Liebert CW Installer User Guide...