6 EC FANS AND PLENUMS
Depending onthe air-distributionoptions of your unit, youmay have EC fans and/or plenums to install.
6.1 Downflow Units with EC Fans
CWdownflow models are equipped withEC fans that may operate inthe fully-raised positionor lowered into the floor stand
for increased efficiency from reduced air resistance.
WARNING! Risk of very heavy 125-lb (56.7-kg) fan modules dropping downward suddenly. Can
cause injury or death. Support fan modules before removing mounting hardware. Use caution
to keep body parts out of the fan modules pathway during repositioning. Only properly trained
and qualified personnel should work on this equipment.
CAUTION: Risk of improper handling of heavy and lengthy parts. Can cause personal injury and
equipment damage. Cabinet panels can exceed 5 ft (1.5 m) in length and weigh more than 35 lb
(15.9 kg). Follow relevant OSHA lifting recommendations and consider using a two-person lift
for safe and comfortable removal and installation of cabinet panels. Only properly trained and
qualified personnel wearing appropriate, OSHA-approved PPE should attempt to remove or
install cabinet panels.
NOTE: Use fans either in their original raised position or with the fans in their fully-lowered position.
Suspension of fans in an intermediate position will directly affect product performance and is not
recommended.
6.1.1 Lowering the EC Fans into the Floor Stand on Downflow Models
NOTE: If your floor-stand height is between 9 in. (228.6 mm) and 21 in. (533.5 mm), please contact the
factory before attempting to lower the fans into the floor stand. If the floor-stand height is 24 in.
(609.6 mm) up to 48 in. (1219.2 mm), the fans can be installed and lowered into the floor stand.
Tools Needed
•
1/2-in. hex socket and wrench
•
Factory-supplied jack, crank and jack support
•
Cable tie cutter
To lower the fans:
1. Remove the middle and bottom panels from the front of the unit.
2. For ease of fanlowering, We recommend removing the infrared humidifier.
3. Positionthe factory-supplied jack and jack support under the fanto be lowered.
4. Raise the jack to safely support the fanbefore removing any hardware.
6 ECFans and Plenums
41
Содержание Liebert CW 038
Страница 14: ...Vertiv Liebert CW Installer User Guide 14 Thispageintentionally left blank...
Страница 22: ...Vertiv Liebert CW Installer User Guide 22 Thispageintentionally left blank...
Страница 38: ...Vertiv Liebert CW Installer User Guide 38 Thispageintentionally left blank...
Страница 44: ...Figure 7 2 Lowering EC fans into floor steps 8 through 9 Vertiv Liebert CW Installer User Guide 44...
Страница 80: ...Vertiv Liebert CW Installer User Guide 80 Thispageintentionally left blank...
Страница 102: ...Vertiv Liebert CW Installer User Guide 102 Thispageintentionally left blank...
Страница 105: ...2 Check contactorsfor pitting Replaceifpitted 3 Check Re torquewireconnections 11 PreventiveMaintenanceChecklist 105...
Страница 108: ...Vertiv Liebert CW Installer User Guide 108 Thispageintentionally left blank...
Страница 167: ...Vertiv Liebert CW Installer User Guide...