9 TROUBLESHOOTING
WARNING! Risk of electric shock. Can cause equipment damage, injury or death. Open all local
and remote electric power supply disconnect switches and verify with a voltmeter that power is
off before working within any electric connection enclosures. Service and maintenance work
must be performed only by properly trained and qualified personnel and in accordance with
applicable regulations and manufacturers’ specifications. Opening or removing the covers to
any equipment may expose personnel to lethal voltages within the unit even when it is
apparently not operating and the input wiring is disconnected from the electrical source.
NOTICE
Risk of improper control circuits. Cancause equipment damage.
Whenusing jumpers for troubleshooting, always remove jumpers whenmaintenance is complete. Jumpers left
connected could override controls and cause equipment damage.
Symptom
Possible Cause
Check or Remedy
Blowerwill not start
Nomainpower
Check L1, L2 andL3 forratedvoltage.
Check Liebert®CWforunit status(Stand-by, Unit Off, MonitoringOff orRemote Off).
Blownfuse ortrippedcircuit
breaker(CB)
Check fusesorCBstomainfan.
Overloadstripped(mainpanel
onLiebert®CW)
Pushreset buttononmainfanoverload. Check amp. draw.
Nooutput voltage from
transformer
Check for24VACbetweenP24-2 andP24-1. If novoltage, check primary voltage.
Control fuse blownorcircuit
breakertripped
Check for24VACbetweenP4-4andE1. If novoltage, check forshort. Replace fuse orreset
circuit breaker.
Blowerrunsbut
controlswill not
operate
Relay R1 not makingcontact
(standardcontrolsonly)
Check for24VACbetweenP36-9andP36-10. If voltage isnot present, R1 isnot receiving
power.
Check airswitch. JumperP36-4toP36-7 If R1 closes, airswitchisnot closing(check for
blowerrotation, loose wiringandpinchedtubing.)Remove jumper.
Check for24VACat R1 coil. If the voltage ispresent andR1 isnot pulling, replace R1.
Table 10.1 Blower troubleshooting
9 Troubleshooting
77
Содержание Liebert CW 038
Страница 14: ...Vertiv Liebert CW Installer User Guide 14 Thispageintentionally left blank...
Страница 22: ...Vertiv Liebert CW Installer User Guide 22 Thispageintentionally left blank...
Страница 38: ...Vertiv Liebert CW Installer User Guide 38 Thispageintentionally left blank...
Страница 44: ...Figure 7 2 Lowering EC fans into floor steps 8 through 9 Vertiv Liebert CW Installer User Guide 44...
Страница 80: ...Vertiv Liebert CW Installer User Guide 80 Thispageintentionally left blank...
Страница 102: ...Vertiv Liebert CW Installer User Guide 102 Thispageintentionally left blank...
Страница 105: ...2 Check contactorsfor pitting Replaceifpitted 3 Check Re torquewireconnections 11 PreventiveMaintenanceChecklist 105...
Страница 108: ...Vertiv Liebert CW Installer User Guide 108 Thispageintentionally left blank...
Страница 167: ...Vertiv Liebert CW Installer User Guide...