![Vertiv Liebert CW 038 Скачать руководство пользователя страница 121](http://html1.mh-extra.com/html/vertiv/liebert-cw-038/liebert-cw-038_installer-and-user-manual_1008217121.webp)
REV : 4
REV DATE : 6/19
DPN002434
Page :1 /1
DOWNFLOW CW300 & CW400 MODELS W/ EC FANS
F
or
m
N
o.
: D
P
N
00
10
40
_R
E
V
4
PRIMARY CONNECTION LOCATIONS
LIEBERT CW
Front View
ALL DIMENSIONS FROM
FRONT CORNER OF UNIT
INCLUDING PANELS
E2
CD1
LV1
LV2
O
X
Y
A
A
Section A-A Top View Front of Unit
CWS1
CWR1
46"
1168mm
122"
3099mm
LV3
E1
CD2
CWS2
CWR2
92"
2337mm
POINT
DESCRIPTION
X
Y
CONNECTION SIZE / OPENING
CONDENSATE DRAIN
1-1/4" NPT Female
W/ OPTIONAL PUMP
1/2" O.D. Cu
CONDENSATE DRAIN
1-1/4" NPT Female
W/ OPTIONAL PUMP
1/2" O.D. Cu
2-WAY CHILLED WATER SUPPLY
3-WAY CHILLED WATER SUPPLY
2-WAY CHILLED WATER SUPPLY
3-WAY CHILLED WATER SUPPLY
2-WAY CHILLED WATER RETURN
3-WAY CHILLED WATER RETURN
2-WAY CHILLED WATER RETURN
3-WAY CHILLED WATER RETURN
E1
9" (229mm)
E2
12" (305mm)
LV1
11" (279mm)
LV2
9-1/2" (241mm)
LV3
8" (203mm)
3-1/8"
2"
7/8"
12" (305mm)
5" (127mm)
119-1/2" (3035mm)
12" (305mm)
57" (1449mm)
10" (254mm)
CD 1
CWS1
CWR1
CD 2
CWS2
4" (102mm)
CWR2
55" (1397mm)
17" (432mm)
62" (1575mm)
ELECTRICAL CONN. (HIGH VOLT)
ELECTRICAL CONN. (LOW VOLT)
Notes:
1. Drawing not to scale. Tolerance on all piping dimensions is ± (13mm) 1/2".
2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap
external to the unit. Select appropriate drain system materials. The drain line must comply with all local codes.
2
2
EC Fan
Outlet
EC Fan
Outlet
EC Fan
Outlet
EC Fan
Outlet
EC Fan
Outlet
EC Fan
Outlet
Содержание Liebert CW 038
Страница 14: ...Vertiv Liebert CW Installer User Guide 14 Thispageintentionally left blank...
Страница 22: ...Vertiv Liebert CW Installer User Guide 22 Thispageintentionally left blank...
Страница 38: ...Vertiv Liebert CW Installer User Guide 38 Thispageintentionally left blank...
Страница 44: ...Figure 7 2 Lowering EC fans into floor steps 8 through 9 Vertiv Liebert CW Installer User Guide 44...
Страница 80: ...Vertiv Liebert CW Installer User Guide 80 Thispageintentionally left blank...
Страница 102: ...Vertiv Liebert CW Installer User Guide 102 Thispageintentionally left blank...
Страница 105: ...2 Check contactorsfor pitting Replaceifpitted 3 Check Re torquewireconnections 11 PreventiveMaintenanceChecklist 105...
Страница 108: ...Vertiv Liebert CW Installer User Guide 108 Thispageintentionally left blank...
Страница 167: ...Vertiv Liebert CW Installer User Guide...