Vertiv
|
eSure™ Power Extend Converter Mounting Bracket Kit Installation Manual (IM565460)
|
Rev. D
33
Parallel Power Extend Converter Installation – Bottom Row
To install a single power extend converter in the bottom row, refer to the procedure “Single Power Extend
Converter Installation – Bottom Row” starting on page 28.
Procedure
[ ] 1.
If the power extend converter is to be installed for a newly connected load, connect the load and
load return cables for the position to be occupied by the power extend converter. At the same time,
connect the power extend converter return wire faston tab (P/N 565990) provided with the power
extend converter to the cabinet’s return busbar (use the same location as the return lead to the
load). At the same time, connect the power extend converter paralleling busbar (P/N 60016097 for
paralleling two converters, P/N 545346 for paralleling three converters) ordered separately to the
distribution panel load busbars (use the same location as the load lead to the load). See
Torque hardware as indicated in
[ ] 2.
If the power extend converter is to replace an existing circuit breaker, remove the circuit breaker
and verify the load and return cables for the position are wired and labeled correctly. At the same
time, connect the power extend converter return wire faston tab (P/N 565990) provided with the
power extend converter to the cabinet’s return busbar (use the same location as the return lead to
the load). At the same time, connect the power extend converter paralleling busbar (P/N 60016097
for paralleling two converters, P/N 545346 for paralleling three converters) ordered separately to the
distribution panel load busbars (use the same location as the load lead to the load). See
Torque hardware as indicated in
[ ] 3.
Connect the return wire (P/N 564330) and 4-inch long return wire jumper (P/N 565752) provided
with
each
power extend converter to the power extend converter return wire faston tab (P/N
565990) installed on the cabinet’s return busbar in the step above. Do this for all power extend
converters. See
NOTE!
The power extend converter is also furnished with an 8-inch long return wire jumper P/N
566207. The 8-inch long return wire jumper is not used with this mounting bracket kit. It is used in
other kits.
[ ] 4.
Route the return wires (P/N 564330) down and behind the top distribution row, then connect them
to the power extend converters. See
. Orient the white square on the return wire faston