Single Power Extend Converter Installation – Bottom Row
To parallel power extend converters in the bottom row, refer to the procedure “Parallel Power Extend Converter
Installation – Bottom Row” starting on page 33.
Procedure
[ ] 1.
If the power extend converter is to be installed for a newly connected load, connect the load and
load return cables for the position to be occupied by the power extend converter. At the same time,
connect the power extend converter return wire faston tab (P/N 565990) provided with the power
extend converter to the cabinet’s return busbar (use the same location as the return lead to the
load). See
. Torque hardware as indicated in
[ ] 2.
If the power extend converter is to replace an existing circuit breaker, remove the circuit breaker
and verify the load and return cables for the position are wired and labeled correctly. At the same
time, connect the power extend converter return wire faston tab (P/N 565990) provided with the
power extend converter to the cabinet’s return busbar (use the same location as the return lead to
the load). See
. Torque hardware as indicated in
[ ] 3.
Connect the return wire (P/N 564330) and 4-inch long return wire jumper (P/N 565752) provided
with the power extend converter to the power extend converter return wire faston tab (P/N 565990)
installed on the cabinet’s return busbar in the step above. See
NOTE!
The power extend converter is also furnished with an 8-inch long return wire jumper P/N
566207. The 8-inch long return wire jumper is not used with this mounting bracket kit. It is used in
other kits.
[ ] 4.
Route the return wire (P/N 564330) down and behind the top distribution row, then connect it to the
power extend converter. See
. Orient the white square on the return wire faston