+24 VDC Power System User Manual (Section 6013)
|
Rev. G
96
Calibrating Battery Charge Digital Temperature Compensation Maximum Voltage
Local MCA Control Panel Adjustment Procedure
1.
All controls are located on the MCA Interface Pad. Refer to
2.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
3.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CALIBRATION
MENU" is displayed.
4.
Press and release the FUNCTION SET ENTER pushbutton.
5.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "MAX W/T =
##.## V" is displayed.
6.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The
“MAX W/T =" portion of the display flashes.
7.
Observe the value displayed. This is the Battery Charge Digital Temperature Compensation maximum
voltage setting. To change this value, press and hold the FUNCTION SET YES (+) or NO (-) pushbutton.
Release the pushbutton when the desired value is displayed.
NOTE!
Refer to Battery and Equipment Manufacturers’ recommendations or site requirements for the
value.
NOTE!
Maximum Voltage with Temperature Compensation is prevented from being adjusted higher
than 0.5V below the High Voltage Shutdown setting, or lower than the float voltage setting.
The MCA is used in various applications, this setting cannot be adjusted beyond the limits of the
Rectifier Module.
8.
With the desired maximum voltage with temperature compensation value being displayed, press and
release the FUNCTION SET ENTER pushbutton.
9.
“ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton. The
display stops flashing.
NOTE!
The maximum voltage with temperature compensation value will not be changed and the
adjustment mode will be exited if the FUNCTION SET YES (+) pushbutton is not pressed within 10
seconds of the “ARE YOU SURE? +
-” prompt.
10.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the
beginning of the MCA menu tree.