+24 VDC Power System User Manual (Section 6013)
|
Rev. G
26
MCA
Menu
Tree
Line No.
(Section
6022)
Message Displayed
Associated
with...
Definition
Can this value
be changed?
50
PCU## FAN FAIL
PCU
Detail Menu
Displays if Rectifier Module (PCU)
fan failed.
## = the designation of the Rectifier
Module (PCU).
No
51
PCU## BRKR OFF
PCU
Detail Menu
not used in this system
No
52
PCU## HVS ACTIVE
PCU
Detail Menu
Displays if Rectifier Module (PCU) in
high voltage shutdown.
## = the designation of the Rectifier
Module (PCU).
No
53
PCU## A/D FAIL
PCU
Detail Menu
Displays if Rectifier Module (PCU)
internal A/D circuit failed.
## = the designation of the Rectifier
Module (PCU).
No
54
PCU## CONVERTER
PCU
Detail Menu
Displays if Rectifier Module (PCU)
internal converter circuit failed.
## = the designation of the Rectifier
Module (PCU).
No
55
PCU## HIGH TEMP
PCU
Detail Menu
Displays if Rectifier Module (PCU)
high temperature alarm active.
## = the designation of the Rectifier
Module (PCU).
No
56
PCU## OPEN SENSE
PCU
Detail Menu
Displays if an external sense lead
opens.
## = the designation of the Rectifier
Module (PCU).
No
57
PCU## SWITCH OFF
PCU
Detail Menu
not used in this system
No
58
PCU## NO REPLY
PCU
Detail Menu
Displays if the Rectifier Module’s
(PCU’s) communications link is lost.
## = the designation of the Rectifier
Module (PCU).
No
59
PCU ALARM MENU
PCU
Detail Menu
Moves you back to this menu.
No
60
NORMAL DISPLAY
PCU
Detail Menu
Moves you to the beginning of the
MCA Menu Tree. "SYSTEM OK" or
"## ALARMS ACTIVE" is displayed.
No
61
SYSTEM ###.##VDC
Measurement
Menu
Displays system output voltage.
## = value.
No