Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
38
MCA
Menu
Tree
Line No.
(Section
6022)
Message Displayed
Associated
with...
Definition
Can this value
be changed?
PLEASE WAIT…
reported until "VERIFY INVENTORY"
is re-entered, and this operation is
completed.
Example: If a Rectifier Module (PCU)
is removed from the system, "PCU**
TYPE ###A" will change to reflect
this but the PCU will not be removed
from the MCA's inventory until
"VERIFY INVENTORY" is entered and
the "UPDATE INVENTORY"
operation is completed.
Press the FUNCTION SELECT UP or
DOWN arrow pushbutton to display
this entry. Press the ALARM
CUTOFF and FUNCTION SET
ENTER pushbuttons simultaneously
to activate this operation. At the
"ARE YOU SURE? + -" prompt, press
either the FUNCTION SET YES (+)
pushbutton to perform the operation,
or the FUNCTION SET NO (-)
pushbutton to cancel this operation.
or
"REPLACE ## PCUs?" is
automatically displayed when a new
Rectifier Module (PCU) is detected
and a PCU no reply alarm is active, or
becomes active within two minutes.
The message is displayed for 2
minutes. [The message timer is
restarted every time a new PCU is
detected or a new PCU no reply
alarm becomes active.]
The timer is terminated and the ALM
## PCUs FAIL message is displayed
if the NO (-) pushbutton is pressed.
PCUs equal to the number of new
PCUs or the number of PCU no reply
alarms, whichever is less, are
removed from the inventory if the
YES (+) pushbutton is pressed or if
the timer expires without a push-
button being pressed. The MCA