Starting and Stopping System Operation
Rectifier Module Normal Starting Procedure
Procedure
1.
Apply input power to the Rectifier Module or insert the Rectifier Module into the shelf.
Rectifier Module Stopping Procedure (Local)
Complete Shutdown
1.
Remove input power from the Rectifier Module or remove the Rectifier Module from the shelf.
Local TR Shutdown
NOTE!
When a Rectifier Module (PCU) is shut down via the Local TR Shutdown feature, it must
be manually restarted (by turning AC power to the Rectifier Module off then on, or by removing
and re-inserting the Rectifier Module). The Local TR Shutdown feature DOES NOT automatically
restart Rectifier Modules to deliver current in any operational or alarm state of the DC plant. The
Rectifier Module must be manually restarted by navigating the MCA and selecting to turn the
Rectifier Module back ON as detailed in the following procedure.
1.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
2.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "CONFIGURE
MENU" is displayed.
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "SET PCU (Rectifier
Module) ON / OFF".
5.
Press and release the FUNCTION SET ENTER pushbutton.
6.
Repeatedly press and release the FUNCTION SELECT UP or DOWN arrow pushbutton until the Rectifier
Module to be stopped using the local TR feature is displayed.
7.
With this Rectifier Module being displayed, press and release the ALARM CUTOFF and FUNCTION SET
ENTER pushbuttons simultaneously.
8.
"ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
9.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the
beginning of the MCA menu tree.
10.
Repeat this procedure to restart the Rectifier Module.