Vertiv
|
+24 VDC Power System User Manual (Section 6013)
|
Rev. G
53
3.
Press and release the FUNCTION SET ENTER pushbutton.
4.
Repeatedly press and release the FUNCTION SELECT DOWN arrow pushbutton until "TEST/EQ HRS =
##" or "TEST/EQ MAN STOP" is displayed.
NOTE!
If "TEST/EQ MAN STOP" is displayed, the system is already set for manual test/equalize. In this
case, proceed with step 9).
NOTE!
If "END TEQ ##.##HRS" is displayed, the system is set for manually initiated timed test/equalize,
and a timed test/equalize is in progress. In this case, you can proceed with steps 5) through 8) to cancel
the timed test/equalize in progress and change the current setting, or proceed with step 9) to proceed
with the timed test/equalize in progress and make no changes.
5.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously. The
"TEST/EQ HRS =" portion of the display flashes.
6.
Press the FUNCTION SET YES (+) pushbutton until the value displayed increases above 99, then
release the pushbutton. "TEST/EQ MAN STOP" is displayed.
7.
Press and release the FUNCTION SET ENTER pushbutton.
8.
“ARE YOU SURE? + -” is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
9.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the
beginning of the MCA menu tree.
Placing the System into Test/Equalize Mode: Manually place the system into test/equalize mode by
navigating to and activating the "SET TEST/EQ MODE" menu item in the MCA function menu. The system is
placed in the test/equalize mode and must be manually placed back to the float mode. A step-by-step
procedure is provided next.
1.
With "SYSTEM OK" being displayed on the MCA Interface Pad, press and release the FUNCTION SET
ENTER pushbutton.
or
With "## ALARMS ACTIVE" being displayed on the MCA Interface Pad, press and release the
FUNCTION SET ENTER pushbutton. Repeatedly press and release the FUNCTION SELECT DOWN
arrow pushbutton until "FUNCTION MENU" is displayed. Press and release the FUNCTION SET ENTER
pushbutton.
NOTE!
In the following step, if "SET FLOAT MODE" is displayed, the system is already operating in the
test/equalize mode. In this case, DO NOT perform steps 2) through 4), proceed with step 5).
2.
Press and release the FUNCTION SELECT DOWN arrow pushbutton to display "SET TEST/EQ MODE".
3.
Press and release the ALARM CUTOFF and FUNCTION SET ENTER pushbuttons simultaneously.
4.
"ARE YOU SURE? + -" is displayed. Press and release the FUNCTION SET YES (+) pushbutton.
5.
Press and release the FUNCTION SET YES (+) and NO (-) pushbuttons simultaneously, to return to the
beginning of the MCA menu tree.